Use of the AXC F 2152 controller under extreme ambient conditions
107708_en_08 PHOENIX CONTACT 103 / 113
A 4 Use of the AXC F 2152 controller under extreme
ambient conditions
The AXC F 2152 controller has been tested successfully over 250temperature change cy-
cles in accordance with IEC 61131-2 in the range from -40°C to +70°C.
The following conditions were observed:
The Axioline F devices for all connecting cables were connected with a minimum con-
ductor cross section of 0.5 mm²
The Axioline F station was assembled on a wall-mounted horizontal DIN rail
Fans were used to ensure continuous movement of air in the control cabinet
The Axioline F station was not exposed to vibration or shock
The Axioline F station was operated with a maximum of 24.5 V (ensured by using
regulated power supply units)
Figure 14-1 Temperature change cycle
Temperature in the control cabinet/ambient temperature
Cycle
1
3 h
+
30 min
3 h
+
30 min
t
1
t
1
(3 0,6) K/min
+
3 K
+
T
min
2 K
+
T
max

Table of Contents

Other manuals for Phoenix Contact AXC F 1152

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Phoenix Contact AXC F 1152 and is the answer not in the manual?

Phoenix Contact AXC F 1152 Specifications

General IconGeneral
BrandPhoenix Contact
ModelAXC F 1152
CategoryController
LanguageEnglish

Related product manuals