DH+/RIO OPTICAL COMMUNICATION MODULES USERS MANUAL
Copyright © 2003 by Phoenix Digital Corporation, All Rights Reserved.
J4 CONNECTOR STANDALONE, PANELMOUNT OCM
PIN # DIAGNOSTIC OUTPUT
(1)
1, 2 Channel A Error (ERR)
3, 4 Channel A Impending Fault Detect (IFD)
5, 6 Channel B ERR
7, 8 Channel B IFD
(1) Each diagnostic output is provided as a normally open FORM A contact
on the designated pair of J4 pin numbers. When a diagnostic function
is asserted (i.e. error or impending fault) the corresponding contact will
close.
Diagnostic Select Switch SW4-1 must be set ON (active) to
enable diagnostic relay outputs.
STANDALONE, PANELMOUNT OCM J4 CONNECTOR
DIAGNOSTIC OUTPUT PIN DEFINITIONS
TABLE 10
1-23