EasyManua.ls Logo

PHOENIX DIGITAL OCM-DPR-1 - Page 27

Default Icon
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DH+/RIO OPTICAL COMMUNICATION MODULES USERS MANUAL
Copyright © 2003 by Phoenix Digital Corporation, All Rights Reserved.
RSLogix 5 OCM I/O module configuration is similar to other types of 1771 I/O modules. The first
step is to select “I/O Configuration” for the 1771 Chassis. Next select the chassis and I/O slot where
the OCM is located, and open the “Edit Module - Module Type” configuration table. From this
table select either “1771-SIM - 8pt Discete I/O Simulator” if OCM Processor Write is Enabled (SW
4 Position 9 ON), or “1771-IG - 5v DC TTL 8pt Input” if OCM Processor Write is Disabled (SW
4 Position 9 OFF). (Note: User should consult Rockwell Allen-Bradley Hardware Installation Manual
for more information on addressing modes and program configuration for I/O Groups, Chassis, and
Racks.)
Read/Write Diagnostic Status and Control functions for the 1771 Plug-In OCM Module are given in
the Diagnostic I/O Bit Map illustrated in Figure 9. Definitions of Diagnostic Select Switch
Settings are provided in Table 9. Specifications and further explanation of OCM diagnostic func-
tions are provided in Sections 1.3.3.5-1.3.3.10.
1.3.3.3 1746 PLUG-IN OLCs (Modules with “-D” Diagnostic Option Only)
Activation, control, and monitoring of 1746 Plug-In OLC diagnostics is provided under program
control thru read/write status and control bytes in the PLC I/O Image Table, and is also provided
under manual control via Diagnostic Select Switch Settings given in Table11. The 1746 Plug-In OLC
(with “-D” Option) occupies a single I/O module slot, and simulates either an 8 bit bi-directional I/O
module (when OLC Processor Write is Enabled) or an 8 bit input module (when OLC Processor
Write is Disabled). The 1746 I/O module designation, density, and type are program configurable,
and must be configured to match the I/O modules in the system... prior to programming. If the 1746
Plug-In OLC module is configured to simulate an 8 bit bi-directional I/O module (ie. SW 2 VALUE
3 is selected), then the module designation is “OTHER”, I/O Mix Code = “19”, and I/O Type Code
= “35”. (Example: If the 1746 Plug-In OLC Module is in I/O slot 1 then the correct configuration for
this slot would be “Slot 1 = OTHER 1935”.) If the 1746 Plug-In OLC module is configured as an 8
bit input module (ie. SW 2 VALUE 7 is selected) then the module designation is “OTHER”, I/O Mix
Code = “19”, and the I/O Type Code = “00”.
RSLogix 500 OLC I/O module configuration is similar to other types of 1746 I/O modules. The first
step is to select “I/O Configuration” for 1746 Chassis. Next select the chassis and I/O slot where the
OLC is located. This will also open an “I/O Configuration” table which will show “Current Cards
Available”. From this table select “Other - Requires I/O Card Type ID”, which will prompt you to
“Enter the I/O Card’s ID (decimal);”. If OLC Processor Write is Enabled (see Diagnostic Switch
Designations in Table 11) enter “1935”. If OLC Processor Write is Disabled enter “1900”. (Note:
User should consult Rockwell Allen-Bradley Hardware Installation Manual for more information on
addressing modes and program configuration for I/O Groups, Chassis, and Racks.)
1-24