Commissioning
Operating Manual PNOZ mc1p
20879-EN-09
| 12
6 Commissioning
6.1 General wiring guidelines
The wiring is defined in the circuit diagram in the Configurator.
Please note:
} 2 connection terminals are available for each of the supply connections 24 V and 0 V.
This means that the supply voltage can be looped through several connections. The cur-
rent at each terminal may not exceed 3 A.
} Outputs OA0 to OA15 are auxiliary outputs using semiconductor technology.
} Use copper wiring with a temperature stability of 75 °C.
} Information given in the Technical details [ 14] must be followed.
6.2 Download modified project to the PNOZmulti system
As soon as an additional expansion module has been connected to the system, the project
must be amended in the PNOZmulti Configurator and downloaded back into the base unit.
Proceed as described in the operating manual for the base unit.
NOTICE
For the commissioning and after every user program change, you must
check whether the safety devices are functioning correctly.
6.3 Connection
Supply voltage AC DC
Supply voltage
OA0
L-
L-
OA1
Semiconductor outputs

Related product manuals