Appendix
Operating Manual PSEN opII3H Series
1003503-EN-08
| 86
[7] Muting sensor 4
[8] Danger zone
[9] Guard to prevent access to the danger zone
[10] Conveyor
a Distance a, muting sensor 1 from muting sensor 2
b Distance b, muting sensor 2 from protected field
d Distance d, muting sensor 3 from protected field
e Distance e, muting sensor 4 from muting sensor 3
f Distance f between two objects that are being transported through the protected
field
L Length of the object that triggers the muting state as it passes the muting sensors
A Working distance A between the safety light curtain's transmitter and receiver
Comply with the following distances and times
} Working distance A between the safety light curtain's transmitter and receiver
When using the PSEN opII T Muting Set < 3000mm
} a = Distance of muting sensor 1 from muting sensor 2
Recommendation in IEC 62046 > 250 mm
} b = Distance of muting sensor 2 from protected field
When using the PSEN opII T Muting Set > 100mm
Recommendation in IEC 62046 < 200 mm
} d = Distance of protected field from muting sensor 3
When using the PSEN opII T Muting Set > 100mm
} e = Distance of muting sensor 3 from muting sensor 4
When using the PSEN opII T Muting Set > 100mm
} L = Length of the object that triggers the muting state as it passes the muting sensors
L> a + b + d + e
} a + b + d + e > 500 mm (recommendation in IEC 62046)
} f = Distance between two objects that are being transported through the protected field
f > a + b + d + e