INSTALLATION
C-16
MacR6-Z0 – USER MANUAL
• Place the dedicated by the gas meter manufacturer pulse emitter, or connect the plug to the rotary or
turbine gas meter pulse output
• Replace the plug inside the device cover by the cable gland with external sealing ring.
o Remove the plug
o insert the cable gland to the cover, and tighten it with 0,3Nm momentum - required key 14mm
Plug and PG7 cable gland in MacR6-Z0 recorder
• Put the pulse emitter cable through cable gland. The diameter of the cable must fit the range from 3,5
to 6mm. Tighten the cable inside the gland using 13mm key simultaneously not letting the gland rotating
itself in the recorders cover.