SELECTED CHAPTERS FROM THE BOILER OPERATION
FILLING THE FEEDER F1 WITH PELLETS
Here are the steps how to fill fuel transportation ways by operating feeders F1 and F2, see procedure in the table
below:
Step button pushed the display shows Note
1
ENTER
1. Direct control
2
ENTER
Feeder 1 OFF
3 up arrow Feeder 2 OFF
4
ENTER
Feeder 2 ON
5 down arrow Feeder 1 OFF
6
ENTER
Feeder 1 ON
7 right arrow set the timer for feeder 1 operation (>10s) according to the feeder length.
8 As soon as you hear a noise of pellets falling from the feeder into the burner, do
9
ENTER
Feeder 1 OFF
10 ESC 1. Direct control
11 ESC MANUAL
12 AUTO / MANUAL AUTO (MOD, EKV)
BOILER IGNITION - BY ELECTRIC IGNITION
Step button pushed the display shows Note
1 START START !
2 ENTER AUTO <I> (MOD, EKV) flashing <I> / indicates that el. spirals are operating
Note:
Only the operator can terminate an ongoing automatic ignition routine by switching into
MANUAL mode.
In such a case, THE ATTENDANT IS OBLIGED TO
remove any fuel that has been fed in the last ignition cycle
from the burner PRIOR TO ANOTHER IGNITION
.
It is necessary to apply the above described procedure even if the energy supply is interrupted during the ignition
process !!!
SETUP OF THE TIME WINDOW FOR SW TANK
Step button pushed the display shows Note
1
ENTER
1. Direct control
2 down arrow - 5x Menu 5 Boiler active
3
ENTER
1. Time zone I
4
ENTER
5 by arrow keys set up the time HH:MM of the beginning of the window and
HH:MM of the end of the window
6
ENTER
7 ESC - 5x
8
AUTO / MANUAL
AUTO (MOD, EKV)
Note:
The boiler will start to heat the SW tank in the set window, once the thermostat of the SW tank is
active.
Note:
Heating of hot water will be terminated upon a signal from the boiler's thermostat. It can occur even
after the time window is closed.