The primary pump is only switched on if the boiler temperature is
above the set DHW temperature. If the boiler temperature drops
below the DHW nominal setpoint minus the DHW switching difference,
charging pump is switched off again.
Off: The function is switched off.
Always: The function is always active.
Automatically: The function is only active if the heat generator cannot
deliver heat or is not available (malfunction, generator lock).
Discharg protec after charg (5042)
If the parameter is at "On", the discharge protection stops the domestic
water pumps Q3 and Q33 from running on as soon as the DHW charging
temperature drops below the storage tank temperature B3.
Charging temp max (5050)
With this setting, the maximum charging temperature for the connected
storage of the solar system is limited. If the DHW-charging value is
exceeded, the collector pump switches off.
Important
The collector pump can be re-activated by the collector
overheating protection function (see programme no. 3850) until
the storage tank safety temperature (90 °C) has been reached.
For more information, see
Collector overtemp prot (3850), page 107
Recooling temp (5055)
Once a recooling function has been activated, it remains in operation until
the set Recooling temp in the domestic water storage tank has been
reached.
Recooling collector (5057)
Recooling of the overhaeted collector through giving off of the energie to
the surrounding of the collector.
El imm heater optg mode (5060)
Substitute: The DHW is only heated by an immersion heater if the boiler
signals a malfunction or a boiler lock exists.
Summer: The DHW is heated by an immersion heater if all connecting
heating circuits have switched to summer mode. As soon at least one
heating circuit is switched to heating mode, the DHW preparation is
taken over by the boiler again.
Important
The immersion heater is also used if a boiler malfunction occurs or
the boiler is switched off due to a boiler lock.
Always: DHW is heated exclusively by the immersion heater.
El immersion heater release (5061)
24h/day: Immersion heater permanently released
DHW release: Immersion heater released subject to DHW-release (see
prog. no. 1620).
Time program 4/DHW: Release of the immersion heater via the time
programme 4 of the local controller.
El immersion heater control (5062)
External thermostat: The controller continuously releases the domestic
water preparation with immersion heater within the release time,
regardless of the storage tank temperature. The current domestic water
setpoint in the controller has no effect. The required storage tank
temperature must be set at the external thermostats. The manual push
and the Legionella function do not work.