5.7 Assembly of the exhaust gas
system
5.7.1 Assembly with downward slope
The exhaust gas duct must be installed with a slope towards the Paramount , so
that the condensed water can drain from the exhaust gas duct to the central con-
densed water collector of the Paramount.
The min. downward slopes are:
- Horizontal exhaust gas duct: min. 3° (min. 5.5 cm per one metre)
- Outer wall feed-through: min. 1° (min. 2.0 cm per one metre)
5.7.2 Working gloves
Caution! Danger of injury by missing working gloves!
Wearing working gloves is recommended during the assembly work, particularly
while cutting the pipes.
5.7.3 Shortening of the pipes
All pipes and all concentric pipes may be shortened. After cutting off, the ends of
the pipes have to be thouroghly de-burred. When shortening a concentric pipe, a
piece of pipe of a length of 6 cm must be cut off the outer pipe. The spring washer
for centring the inner pipe becomes obsolete.
5.8 Working with the exhaust
gas system KAS
Additional direction changes
Reduction of the total length of the exhaust gas pipe by:
- per 87° elbow = 2.50 m
- per 45° elbow = 1.00 m
- per 30° elbow = 0.50 m
- per 15° elbow = 0.50 m
- per revision T-piece = 2,50 m
Installation
7308272-03 03.14 Paramount three 30-115 kW 31