POWER ELECTRONICS
SD700 PROFIBUS
TRIAL RUN
35
E
N
G
L
I
S
H
The Profibus board sends 46 bytes of input data to the Profibus-DP
Master.
Output
Data
(Word)
Param.
Modbus
Address
Variables
Modbus Range
0
SV1.1
40162
ACTUAL_SPEED_REFERENCE
8192 = 100% of motor rated speed
1
STATUS
LINE
40219
GENERAL_STATUS
0 to 201
2
SV1.7
40163
OUTPUT_MOTOR_CURRENT
Real value = (Modbus value / 10)
3
SV1.8
40164
OUTPUT_MOTOR_TORQUE
8192 = 100% of motor rated torque
4
SV1.10
40165
OUTPUT_MOTOR_POWER
Real value = (Modbus value / 10)
5
SV1.6
40166
OUTPUT_MOTOR_VOLTAGE
Real value = Modbus value
6
SV1.5
40167
OUTPUT_MOTOR_FREQUENCY
Real value = Modbus value
7
SV1.9
40168
MOTOR_COS_PHI
Real value = (Modbus value / 10)
8
SV1.3
40169
MOTOR_SPEED_RPM
Real value = Modbus value
9
SV1.4
40170
MOTOR_SPEED_PERCENTAGE
8192 = 100% of motor rated speed
10
SV2.4
40171
DC_BUS_VOLTAGE
Real value = Modbus value
11
SV2.1
40183RS
40184ST
40185RT
INPUT_VOLTAGE
Real value = Modbus value
12
SV3.1
40183
ANALOG_INPUT_1_VALUE
Real value = (Modbus value / 1000)
13
SV3.4
40187
ANALOG_INPUT_2_VALUE
Real value = (Modbus value / 1000)
14
SV3.7
40192
ANALOG_OUTPUT_1_VALUE
Real value = (Modbus value / 1000)
15
SV3.9
40193
ANALOG_OUTPUT_2_VALUE
Real value = (Modbus value / 1000)
16
SV3.11
40196
DIGITAL_INPUT_STATUS
LSB BIT0 MFI1
BIT6 PTC
0 to 1
17
SV3.12
40197
DIGITAL_OUTPUT_STATUS
BIT 0 R1; Range from 0 to 1
BIT 1 R2; Range from 0 to 1
BIT 2 R3; Range from 0 to 1
18
SV4.9
40232
COMPARATOR1_STATUS
0 to 1
19
40233
COMPARATOR2_STATUS
0 to 1
20
40234
COMPARATOR3_STATUS
0 to 1
21
SV4.6
40204
ACTUAL_CTRL_SETPOINT
8192 = 100% maximum range of Al
22
SV4.7
40205
ACTUAL_FEEDBACK
8192 = 100% maximum range of Al