EasyManua.ls Logo

Powerex MTSD0503 - Page 2

Default Icon
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Scroll Medical & Laboratory Compressed Air Systems
Powerex 150 Producon Drive Harrison, OH 45030 USA
P 1.888.769.7979 F 513.367.3125 www.powerexinc.com
IN907800AV 08/2018
Page 2 of 40
Specicaons (Connued)
HP Air End Discharge Pressure (PSIG)
Air Delivery
(SCFM)
3 SLAE03EB 95-115 (125-145 oponal) 8.8 @ 100 PSIG
7.5 @ 145 PSIG
5 SLAE05E 95-115 (125-145 oponal) 15.2 @ 100 PSIG
5 SLAE05EHP 95-115 (125-145 oponal) 12.5 @ 100 PSIG
NOTE: For system electrical informaon, see wiring diagram
shipped with unit.
Compressor Performance (per basemount)
Breathable Air Warning
This unit is NOT equipped and should NOT be used “as is”
to supply breathing quality air. For any applicaon of air for
human consumpon, you must t the air compressor/pump
with suitable inline safety and alarm equipment. This addional
equipment is necessary to properly lter and purify the air to
meet minimal specicaons for Grade D breathing as described
in Compressed Gas Associaon Commodity Specicaon for air,
OSHA, ANSI and/or Canadian Standards Associaons (CSA).
DISCLAIMER OF WARRANTIES
IN THE EVENT THE COMPRESSOR IS USED FOR THE PURPOSE
OF BREATHING AIR APPLICATION AND PROPER IN-LINE SAFETY
AND ALARM EQUIPMENT IS NOT SIMULTANEOUSLY USED,
EXISTING WARRANTIES ARE VOID, AND POWEREX DISCLAIMS
ANY LIABILITY WHATSOEVER FOR ANY LOSS, PERSONAL INJURY
OR DAMAGE.
For Laboratory Systems
Components
Powerex open scroll systems are designed to supply connuous oil-
free air by using the most advanced scroll technology.
The Powerex scroll compressor oers a dynamically balanced air
end which insures vibraon-free operaon. The rotary design permits
a connuous 100% duty cycle. No oil separaon, oil ltraon, or inlet
valves are required on the Powerex Scroll unit. Each compressor
shall be belt driven oil-less rotary scroll single stage, air-cooled
construcon with absolutely no oil needed for operaon. Direct drive
compressors shall not be used. The rotary design shall not require any
inlet or exhaust valves and shall be rated for 100% connuous duty.
Systems consist of mulple compressor pumps that are automacally
controlled and alternated to equalize usage and wear. Medical
systems have one or more pumps designated as the reserve and their
output is not ulized for normal system capacity rangs.
The Powerex oil-less rotary scroll air compressor is based on the
theory of scroll compression. A scroll is a free-standing, intricate
spiral bounded on one side by a solid, at plane or base. A scroll set,
the basic compression element of a scroll compressor, is made up
of two idencal spirals which form right and le hand parts. One of
these scroll components is indexed or phased 180° with respect to
the other so the scrolls can mesh. Crescent-shaped gas pockets are
formed and bounded by the spirals and the base plate of both scrolls.
As the moving scroll is orbited around the xed scroll, the pockets
formed by the meshed scrolls follow the spiral toward the center
and diminish in size. The moving scroll is prevented from rotang
during this process so that the 180° phase relaonship of the scrolls
is maintained. The compressors inlet is at the outer boundary of the
scrolls. The entering gas is trapped in two completely opposite gas
pockets and compressed as the pockets move toward the center. The
compressed gas is discharged through the outlet at the center of the
xed scroll so no valves are needed.
Compressor systems are ed with single point connecon intake
manifolds. For medical systems the manifold must be connected to
air intake piping located as specied in NFPA99. Lab systems may
ulize room air for the intake. Parcle ltraon is provided by the
intake lter assemblies in each branch of the compressor system.
When remote intake systems take in humid warm air from outdoors,
and route it through air-condioned buildings, water will condense in
the intake piping. NOTICE: Water will destroy the compressor pump
if it is ingested. The air lters will not stop water. Water trapping drip
legs must be designed, installed and maintained by the responsible
pares. The intake system is also equipped with isolaon valves
allowing the line to be closed if a branch is opened for service. The
ball valve handles have been removed and shipped separately to help
avoid accidental closure of the valves when the system is running.
NOTICE Running the pumps with the intake valve closed will damage
the pumps. Powerex recommends that the system be locked out if
the valve is closed.
Each compressor pump is ed with exible connecons on the
intake and exhaust side. The compressed air from each pump is
monitored by a temperature switch that will work with the controls
to shut down the system if the air temperature exceeds design limits.

Related product manuals