EasyManua.ls Logo

Powerex MTSD0503 - Alarm Configuration

Default Icon
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Scroll Medical & Laboratory Compressed Air Systems
Powerex 150 Producon Drive Harrison, OH 45030 USA
P 1.888.769.7979 F 513.367.3125 www.powerexinc.com
IN907800AV 08/2018
Page 22 of 40
Alarm Conguraon
1. Click on the Other dropdown menu and select Alarm Conguraon. Click on the Conguraon Mode buon to edit the alarm sengs.
2. To enable an alarm, check the enable box.
3. If an alarm is enabled, then the Low Alarm and High Alarm must be set.
4. If the value of the point falls below the Low Alarm, the alarm is set and an email is generated if email is congured.
5. If the value of the point reaches the High Alarm, the alarm is set and an email is generated if email is congured.
6. Scroll to the boom and Save Parameters.
7. To save changes and force the gateway back to running mode, click on the Reboot Now buon and aer 5 seconds hit the Refresh buon.
You should see the gateway appear in Mode: Running.

Related product manuals