33GTS Series Uninterruptible Power Manager
• Output frequency – AC mode: Follows Input Inverter mode:
• 50 Hz or 60 Hz. + 0.1 Hz. (determined by power line frequency
prior to outage)
THD (inverter mode) = < 4% on battery
Backup time full load = > 5 min
Efciency (on main) = > 86%
Cooling - Convection
Mechanical Data
Environmental Data
Battery Charger
*To 90% of capacity
24 hours to full charge
VA
Rating
Dimensions
H x W x D
Shipping Weight
North American
(lbs.)
Shipping Weight
International (kg.)
250
in. 6.60 x 5.00 x 13.40 23
mm. 168 x 127 x 340 10.35
400
in. 6.60 x 5.00 x 15.00 28
mm. 168
x 127 x 383 12.70
600
in. 8.00 x 5.75 x 15.50 33
mm. 204 x 146 x 393 15.00
Factor Operating Shipment/Storage
Temperature 0-40° (32°-104°F) -20° - + 60° C (-4° - +140° F)
Humidity 5-90% non-condensing 5-90% non-condensing
Altitude 2,000m (6500 ft.) max. 15,000m (49,000 ft.) max.
250 VA 400 VA 600 VA
(1) 12V 8.5AH (1) 12V 8.5AH (2) 12V 8.5AH
6-10 hours* 6-10 hours* 6-10 hours*