Chapter 5 Control panel and operation
15
closed state before power on, soft starter will not respond the command , you must cancel the
running command by one time ,then give it run command again to make the soft starter work.
When soft starter fault reset, continuous running command is valid. Soft starter will not
respond the running command, you need to removed running command and then the running
protection state is canceled.
State 2:The electrical terminal running protection is invalid: the motor will start automatically
when the external control terminal in the closed state with power on , this is to say allow power on
start.
State 1 is shorted the 2, 3 of J14; state 2 is shorted the 1, 2 of J14.
5-5.Other Settings description
PC is the selection of allowing to modify parameter, there are three options:
1) PC is set to 0, it is prohibited to modify any parameter .
2) PC is set to 1,it is prohibited to modify P4, P6, PD, PE, PP, PU parameters.
3) PC is set to 2, it is allowed to modify all the parameters.
5-6.Help and instructions
Help information as following table:
Display
Explanation
AC:XXX
Three digital voltmeter, to monitor three-phase AC power supply voltage.
45A-380V
The specifications of soft starter is 45A/380V.
H1:E05
Last occurred fault information Err05.
H2:E01
There had been a fault information Err01.
H3:E06
There had been a fault information Err06.
H9:E00
There was no fault information.
Uer3.0
The software version of this product is Ver3.0. With the software upgrading,
version with the increase.
LXXXX
Total number of successful starting.
RUNXX
The spending time (seconds) of last soft starting (Starting successfully) .
Note: H1 ~ H9 with recursive way to storage newly happened nine fault information.
1) In the non-soft start and non-soft stop state, and did not enter the setting mode, press the
Set key, can enter into the Help menu, and then press the UP or DOWN key to select message.
In the help state, press the Set key or Stop button to exit help state..