12 5725V101-IN
Output:
Current output (5725D):
Programmable signal ranges ...................... 0...20, 4...20 &
20...0, 20...4 mA
Load (max.) .................................................. 20 mA / 800 Ω / 16 VDC
Current limit ................................................. ≤ 28 mA
Load stability ............................................... ≤ 0.01% of span / 100 Ω
Programmable response time ..................... 1.0...60.0 sec
Sensor error indication, at Namur input:
selectable .............................................. 0 / 3.5 / 23 mA / none
Output limitation at outside range:
on 4...20 and 20...4 mA signals............. 3.8...20.5 mA
on 0...20 and 20...0 mA signals............. 0...20.5 mA
Relay outputs (5725D):
Relay function.............................................. Setpoint
Hysteresis, in % / display counts ............... 0.1...100% / 1...9999
On and Off delay ......................................... 0...3600 sec
Power On delay ........................................... 1.0...60.0 sec
Sensor error action ...................................... Make / Break / Hold
Max. voltage ................................................ 250 VRMS
Max. current ................................................ 2 A / AC
Max. AC power ........................................... 500 VA
Max. current at 24 VDC............................... 1 A
Approvals:
EMC 2004/108/EC ...................................... EN 61326-1
LVD 2006/95/EC .......................................... EN 61010-1
UL, Standard for Safety .............................. UL 61010-1
GOST R
Marine:
Det Norske Veritas, Ships & Offshore ......... Stand. f. Certific. No. 2.4