DISPLAY NAVIGATIONDISPLAY NAVIGATION
Balancing Menu
Scroll through with the ‘Up’ and ‘Down’ buttons. Press ‘Enter/Menu’ button to apply your changes. ‘...Saving...’ will display as
your changes are applied.
BALANCING
PRESS MENU
TO EXIT
DPR. OVERRIDE
DISABLED
DPR. OVERIDE
GOTO COOL MIN
Cool Min
Regular and LFGH dampers go to their Cool Minimum positions
DPR. OVERIDE
GOTO COOL MAX
Cool Max
Regular and LFGH dampers go to their Cool Maximum positions
DPR. OVERIDE
GOTO HEAT MIN
Heat Min
Regular and LFGH dampers go to their Heat Minimum positions
DPR. OVERIDE
GOTO HEAT MAX
Heat Max
Regular and LFGH dampers go to their Heat Maximum positions
DPR. OVERIDE
GOTO NEUTRAL
Neutral Flow
Regular and LFGH dampers go to their Neutral Supply Air positions
DPR. OVERIDE
GOTO FULL OPN
Full Open
Force all dampers and LFGH full open
DPR. OVERIDE
GOTO FULL CLO
Full Close
Force all dampers and LFGH closed
POSITION
TARGET
• Display shows current target and position
• Controller will remain in this mode until user exits the
menu
VVT Menu
(Pressure Dependent Damper Ranges)
Scroll through with the ‘Up’ and ‘Down’ buttons. Press ‘Enter/Menu’ button to apply your changes. ‘Saving...’ will display as your
changes are applied.
VVT
PRESS MENU
TO EXIT
DPR. RUNTIME
90 SEC.
Damper Runtime
• Damper runtime (time to drive through entire damper range)
• Range: 0-600 seconds Default: 90 seconds
LFGH COOL MIN
0%
LFGH Cool Min Position
• LFGH Cool Minimum Position in %
• Range: 0-100% Default: 0%
LFGH COOL MAX
100%
LFGH Cool Max Position
• LFGH Cool Maximum Position in %
• Range: 0-100% Default: 100%
LFGH HEAT MIN
0%
LFGH Heat Min Position
• LFGH Heat Minimum Position in %
• Range: 0-100% Default: Depends on sequence
LFGH HEAT MAX
100%
LFGH Heat Max Position
• LFGH Heat Maximum Position in %
• Range: 0-100% Default: Depends on sequence
LFGH NEUTRAL
0%
LFGH Neutral Supply Air position (not normally used)
• LFGH position (in %) when Neutral supply air is present
• Range: 0-100% Default: 50%
LFGH RUNTIME
90 SEC
LFGH Neutral Supply Air position (not normally used)
• LFGH Damper runtime (time to drive through entire damper range)
• Range: 0-600 seconds Default: 90 seconds
DPR. COOL MIN
0%
Damper Cool Min Position
• Cool Minimum position in %
• Range: 0-100% Default: 0%
DPR. COOL MAX
100%
Damper Cool Max Position
• Cool Maximum position in %
• Range: 0-100% Default: 100%
DPR. HEAT MIN
0%
Damper Heat Min Position
• Heat minimum position in %
• Range 0-100% Default: 0%
DPR. HEAT MAX
100%
Damper Heat Max Position
• Heat Maximum Position in %
• Range 0-100% Default: 100%
DPR. NEUTRAL
0%
Damper Neutral Supply Air position (not normally used)
• Damper position (in %) when Neutral Supply Air is present
• Range 0-100% Default: 0%
UNOCC DPR POS
33%
Unoccupied Damper Position
• Unoccupied (Night Setback) Damper position in %
• Range: 0-100% Default: 33%