PCM - INTERIOR AND PERIMETER ZONES COOLING AND HEATING - Manual
|
priceindustries.com priceindustries.com
|
PCM - INTERIOR AND PERIMETER ZONES COOLING AND HEATING - Manual
PCM - INTERIOR AND PERIMETER ZONES COOLING AND HEATINGPCM - INTERIOR AND PERIMETER ZONES COOLING AND HEATING
DISPLAY NAVIGATIONDISPLAY NAVIGATION
SET LO LIMIT
65.0°F
Day Setpoint Low Limit
• This is the lowest Setpoint allowed
• Range: 10.0°F – 100.0°F Default: 65.0°F
SET HI LIMIT
80.0°F
Day Setpoint High Limit
• This is the lowest Setpoint allowed
• Range: 10.0°F – 100.0°F Default: 80.0°F
TEMP. UNITS
FEHRENHEIT
Termperature Units
• Fahrenheit or Celsius
• Default: °F
NIGHT HEAT SET
62.0°F
Night Heat Setpoint
• PCM will maintain this heating Setpoint when unoccupied
• Range: 10.0°F – 100.0°F Default: 62.0°F
NIGHT COOL SET
83.0°F
Night Cool Setpoint
• PCM will maintain this cooling Setpoint when unoccupied
• Range: 10.0°F – 100.0°F Default: 83.0°F
PRO. BAND
2.0°F
Proportional Band
• The Proportional Band is the temperature range through which the controller calculates a
0-100% load
• Range: 0.5°F – 25.0°F Default: 2°F
DAY DIFF.
1.0°F
Day Differential
• This is the maximum allowed “error” on either side of the room Setpoint before the controller
will enter its heating or cooling proportional bands
• Range: 0.5°F – 25.0°F Default: 1.0°F
CONTROL FROM
THERMOSTAT
Control Source
• Thermostat: Controller uses thermostat temperature and Setpoint to determine room load and
control
• Analog Input: Controller uses 0-10VDC inputs to determine room load and control. Use this
control source type for a 0-10VDC signal by others.
PRESS MENU
TO EXIT
SETPOINT
Setpoint Menu
(Setpoint Limits and Temperature Units)
Scroll through with the ‘Up’ and ‘Down’ buttons. Press ‘Enter/Menu’ button to apply your changes. ‘Saving...’ will display as your
changes are applied.
SUPPLY AIR TEMP
50.0°F
Supply Air Temperature (S.A.T.) readout
• Shows current thermistor probe reading
• Range: -59.0°F – 300.0°F
• “No Probe” means no sensor is connected
NEUTRAL MODE
FORCE COOL
Neutral Mode
Controls Supply Air calculations by the PCM
NOTE: Default mode is “Force Cool”. This will be used 99.9% of the time.
• Neutral Mode: Dynamic
- When Supply Air Temperature (as measured on thermistor input) is below room temp, it is
considered cold
- When Supply Air Temperature (SAT) is above room temp, it is considered hot
- NOTE: There is a 2 degree differential on either side of the current room temperature
which would equate to Neutral Supply Air if the SAT fell within this range.
• Neutral Mode: Conventional
- Uses hot/cold switch points which are hard set below
- Not recommended
• Neutral Mode: Force Cool
- PCM Default
- Controller assumes cold supply air at all times (despite any reading of T1 Thermistor input)
- This is useful by allowing the T1 thermistor input to be used for monitoring only
• Neutral Mode: Force Heat
- Control assumes hot supply air at all times
- Not recommended
HOT SWITCH
0.0°F
Hot Switch - Only active/visible when Neutral mode = Conventional
• Only active/visible when Neutral mode = Conventional
• PCM will consider the supply air warm if at the hot switch temp or above
• Default: 0.0°F – PCM defaults to Cool supply air at all times
COLD SWITCH
0.0°F
Cold Switch - Only active/visible when Neutral mode = enabled
• Only active/visible when Neutral mode = Enabled
• PCM will consider the supply air cold if at the cold switch temp or below
• Default: 0.0°F – PCM defaults to Cool supply air at all times
RM. TMP. OFFSET
0.0°F
SAT OFFSET
0.0°F
PRESS MENU
TO EXIT
INPUT
Input Menu
(Supply Air Temp and Neutral Mode)
Scroll through with the ‘Up’ and ‘Down’ buttons. Press ‘Enter Menu’ button to apply your changes. ‘Saving...’ will display as your
changes are applied.