9 Sensor LLOP
10 Sensor HWT
11 Sensor Fuel
12 V-DG-N
13 V-DG-B
14 V-DG-Y
15 V-DG-R
16 V-Mains-N
17 V-Mains-B
18 V-Mains-Y
19 V-Mains-R
20 NC
21 NC
22 NC
23 D Input 4
24 D Input 3
25 D Input 2
26 D Input 1
27 Emergency
28 Semi/Auto
29. R Start/Stop
30. Pro Output 3
31. Pro Output 2
32. Pro Output 1
33. Hooter
34. Solenoid
35. Crank
36. GCB
37. MCB
38. Chg. Alt. Contact
39. Battery(+ve)(8-35 V DC)
40. Battery(-ve)
41. Sensor(-ve)
19.0 Technical Specifications
AC voltage withstand 330 VAC (Phase to neutral)
Measurement Accuracy
Voltages & Current 1% of Reading
Power & Energies 2% of Reading
Surge 1.2/50Usec 2.5KV
Battery Voltage 9-35 V DC
DC Interruption time 0.4 Sec
Cut out Dimensions 155mm X 117mm
Depth 41.8 mm
Digital Input Level Battery Voltage (Negative)
20.0 Dimensions
Cat_ECON-06-15 -Ver1.0. Page 20/21