23
NOTE
After installation, do not forget to register online for full warranty:
http://www.pylontech.com.cn/service/support
Caution
1) follow local electric safety and installation policy, a suitable disconnection
device between battery system and inverter could be required.
2) all the installation and operation must follow local electric standard.
5.7 Suitable disconnection device
It is recommended to have a disconnection device for protection between
battery system and inverter:
1) The rated voltage shall ≥60V DC. Do NOT use AC breaker.
2) The rated current shall match with system design:
shall consider:
the maximum DC current on inverter side.
the number of power cable: for instance, if only one pair of 4awg cable,
the rated current of breaker shall be 125A or smaller.
3) If using breaker, the type shall be type C (recommended) or type D.
The Icu required:
the maximum short circuit current for calculation of each module is 2500A.
for instance:
Icu of breaker
1~4 modules Must ≥10kA
5~8 modules Must ≥20kA