APPENDIX A
FM APPROVAL DESCRIPTION
Applicable Documents:
FM 3810: 2005 Elec. and Electronic Test, Measuring, and Process Control Equipment
FM 3600: 2011 Electrical Equipment for use in Hazardous (Classified) Locations
FM 3610: 2010 Intrinsically Safe, Class I, II, III, Div I, Haz. Loc.
FM 3611: 2004 Elec. Equip. for use in Cl. I/II, Div. 2 and Cl. III, Div. 1/2 Haz. Loc.
FM 3615: 2006 Explosion proof Electrical Equipment
FM 3230: 2010 Smoke actuated detectors for automatic alarm signaling
ANSI/ISA 1010-1: 2004 Safety Requirements for Electrical Equipment for Measurement,
Control, and Laboratory Use – Part 1: General Requirements
ANSI/IEC 60529: 2004 Degrees of Protection Provided by Enclosures (IP Code)
ANSI/ISA 60079-0: 2013 Explosive atmospheres – Part 0: Equipment – General Requirements
ANSI/ISA 60079-1: 2013 Explosive atmospheres – Part 1: Equipment protection by Flameproof
Enclosures “d”
ANSI/ISA 60079-11: 2014 Explosive atmospheres – Part 11: Equipment protection by intrinsic
safety “i"
Special Conditions For Safe Use X:
1. The 30-3013 is to be installed in locations where the risk of mechanical damage is low.
2. Potential electrostatic charging hazard please see instructions for proper installation.
3. All unused device openings must be closed using a suitably certified plug.
4. For field connections, use wire rated 20°C greater than maximum ambient temperature.
5. For AEx d rated Model 30-3013 Smoke Detector, the flameproof joints are not allowed to be
repaired per manufacturer's instruction manual.
6. The 30-3013 shall be used with the Q3013D Duct Mount Accessory for duct mount
installations.
30-3013
Class I Div 1 Groups B, C, D T4
Class I Div 2 Groups A, B, C, D T4
Class I Zone 1 AEX db ia IIC T4 Gb
Tamb –20°C to +65°C
IP44
Q3013D Duct Mount Accessory
ANSI/UL 268A: 4th Edition Standard for Smoke Detectors for Duct Applications (only when
installed on the vertical surface of the duct)