NOMINAL EVAPORATOR WATER FLOW
QTC3
TEMPERATURE (°F) WATER FLOW (GPM) AIR ON CONDENSER (°F)
MIN
1
MAX
2
MIN MAX MIN
3
MAX
4
STANDARD EFFICIENCY
3070TSE
40 55 60 325 0 125
3075TSE
40 55 100 350 0 125
3085TSE
40 55 100 400 0 125
3095TSE
40 55 100 400 0 125
3110TSE
40 55 138 525 0 125
3125TSE
40 55 115 530 0 125
3140TSE
40 55 138 525 0 125
3160TSE
40 55 150 625 0 125
HIGH EFFICIENCY
3055THE
40 55 60 325 0 125
3060THE
40 55 60 325 0 125
3079THE
40 55 138 525 0 125
3090THE
40 55 100 400 0 125
3100THE
40 55 100 400 0 125
3120THE
40 55 100 400 0 125
3129THE
40 55 138 525 0 125
3150THE
40 55 138 525 0 125
3170THE
40 55 150 625 0 125
3205THE
40 55 230 625 0 125
3225THE
40 55 220 625 0 125
Design Parameters
NOTES:
1. For leaving liquid temperature below 40°F (4°C) (to 10°F [-12°C]), optional low temperature glycol kit re-
quired. Contact your nearest Quantech Ofce for application requirements.
2. For leaving liquid temperature higher than 55°F (13°C), contact the nearest Quantech Ofce for applica-
tion guidelines.
3. The evaporator is protected against freezing to -20°F (-29°C) with an electric heater as standard.