QTC3040T TO QTC3225T
Air-Cooled Scroll Chillers
with Brazed Plate Heat Exchanger
Style B (60 Hz) 4 to 12 Fan
40 ton to 230 ton
140 kW to 800 kW
R-410A
R-454B
Issue Date:
December 19, 2023
Air-Cooled Scroll Chiller
Installation, Operation, Maintenance
Supersedes: QTC3-NM1 (1123) Form QTC3-NM1 (1223)
Products are produced at a
f aci l it y who s e qu a l it y -
management systems are
ISO9001 certified.
035-24487-000
LD18971a

Table of Contents

Questions and Answers

  • A
    Amy GarciaAug 7, 2025
    What to do if my Quantech QTC3040T has no display on the panel and won't operate?
    • C
      Chad BurgessAug 7, 2025
      If your Quantech Chiller's panel has no display and the unit won't operate, there could be several reasons: 1. There may be no 115 VAC to the 24 VAC Transformer. In this case, check the wiring and fuse 1FU. 2. There may be no 24 VAC to the Microboard. Check the wiring from the Control Transformer to the Microboard. 3. The Control Transformer might be defective, with no 24 VAC output. If so, replace the Control Transformer. 4. There could be a short in the wire to the temperature sensors or pressure transducers. To isolate this, unplug the connections at the IPU II & I/O Board. 5. The IPU II & I/O Board or the Display Board might be defective. Contact Quantech Service before replacing circuit Boards!
  • W
    williamsamberAug 15, 2025
    Why does my Quantech QTC3040T Chiller show a high discharge pressure fault?
    • J
      Joanne OliverAug 15, 2025
      A high discharge pressure fault in your Quantech Chiller can occur due to several reasons: 1. The condenser fans might not be operating or are operating backwards. Check the fan motor and contactors, and ensure the fan blows air upwards. 2. There might be too much refrigerant in the system. If so, remove some refrigerant. 3. There could be air in the refrigerant system. In this case, evacuate and recharge the system. 4. The discharge pressure transducer might be defective. Replace the discharge pressure transducer.
  • R
    Raven BellAug 22, 2025
    What to do if my Quantech QTC3040T shows a low suction pressure fault?
    • R
      Robert JensenAug 22, 2025
      A low suction pressure fault in your Quantech Chiller may arise due to: 1. Improper suction pressure cutouts adjustments. Adjust per recommended settings. 2. Low refrigerant charge. Repair the leak if necessary and add refrigerant. 3. Fouled filter dryer. Change the dryer/core. 4. Defective TXV. Replace the TXV. 5. Reduced flow of chilled liquid through the cooler. Check GPM, check operation of pump, clean pump strainer, purge chilled liquid system of air. 6. Defective suction pressure transducer/low pressure switch or wiring. Replace transducer/low pressure switch or faulty switch or wiring. 7. Defective LLSV. Replace the LLSV.
  • V
    Vanessa BookerAug 29, 2025
    How to fix a Flow Switch/Remote Stop no run permissive on Quantech QTC3040T?
    • J
      Jared MedinaAug 29, 2025
      If your Quantech Chiller displays a Flow Switch/Remote Stop no run permissive, consider these potential causes: 1. There may be no chilled liquid flow. Check the chilled liquid flow. 2. The flow switch might be improperly installed. Ensure the flow switch is installed according to the manufacturer’s instructions. 3. The flow switch itself could be defective. Replace the flow switch. 4. The remote cycling device might be open. Check cycling devices connected to terminals 13 and 14 of the XTBC1 Terminal Block.

Quantech QTC3040T Specifications

General IconGeneral
BrandQuantech
ModelQTC3040T
CategoryChiller