What to do if my Quantech QTC3040T has no display on the panel and won't operate?
- CChad BurgessAug 7, 2025
If your Quantech Chiller's panel has no display and the unit won't operate, there could be several reasons: 1. There may be no 115 VAC to the 24 VAC Transformer. In this case, check the wiring and fuse 1FU. 2. There may be no 24 VAC to the Microboard. Check the wiring from the Control Transformer to the Microboard. 3. The Control Transformer might be defective, with no 24 VAC output. If so, replace the Control Transformer. 4. There could be a short in the wire to the temperature sensors or pressure transducers. To isolate this, unplug the connections at the IPU II & I/O Board. 5. The IPU II & I/O Board or the Display Board might be defective. Contact Quantech Service before replacing circuit Boards!