Section 5: Technical data
Form QTC3-NM1
Issue date: 12/19/2023
55
ETHYLENE GLYCOL PROPYLENE GLYCOL
%
WEIGHT
TONS
COMPR
KW
GPM F/
TON
PRESS
DROP
FREEZE
PT
%
WEIGHT
TONS
COMPR
KW
GPM F/
TON
PRESS
DROP
FREEZE
PT
10.0 1.0 1.0 24.3 1.0 26.2 10.0 1.0 1.0 24.0 1.0 26.0
20.0 1.0 1.0 25.1 1.1 17.9 20.0 1.0 1.0 24.3 1.1 19.0
30.0 1.0 1.0 25.9 1.2 6.7 30.0 1.0 1.0 24.9 1.3 9.0
40.0 1.0 1.0 26.9 1.4 -8.1 40.0 1.0 1.0 25.6 1.4 -6.0
50.0 1.0 1.0 28.0 1.6 -28.9 50.0 0.9 1.0 26.6 1.7 -28.0
NOTE: Water Pressure Drop Curves may extend past the minimum and maximum water ow ranges.
Table 5: Ethylene and Propylene Glycol Correction Factors