Section 1: General chiller information and safety
Form QTC3-NM1
Issue date: 12/19/2023
2
Print calls up to the liquid crystal display
Operating data for the systems
History of fault shutdown data for up to the last
six fault shutdown conditions.
An RS-232 port, in conjunction with this press-to-
print button, is provided to allow hard copy print-
outs using a separate printer (by others).
Entry keys
This section is used to enter setpoints or modify system
values.
Setpoints Keys
Updating can be performed to:
Chilled liquid temperature setpoint and range
Remote reset temperature range
Set daily schedule/holiday for start/stop
Manual override for servicing
Low and high ambient cutouts
Number of compressors
Low liquid temperature cutout
Low suction pressure cutout
High discharge pressure cutout
Anti-recycle timer (compressor start cycle time)
Anti-coincident timer (delay compressor starts)
Unit keys
This section is used to:
Set time
Set unit options
Oper data key
The microprocessor control center is capable of dis-
playing the following:
Return and leaving liquid temperature
Low leaving liquid temperature cutout setting
Low ambient temperature cutout setting
Outdoor air temperature
English or Metric data
Suction pressure cutout setting
Each system suction pressure
Discharge pressure (optional)
Liquid Temperature Reset via a Quantech BAS
DDC or Building Automation System (by others)
using a 4 mA to 20 mA or 0 VDC to 10 VDC input
Anti-recycle timer status for each system
Anti-coincident system start timer condition
Compressor run status
No cooling load condition
Day, date and time
Daily start/stop times
Holiday status
Automatic or manual system lead/lag control

Compressor starts and operating hours
(each compressor)
Status of hot gas valves, evaporator heater
and fan operation
Run permissive status
Number of compressors running
Liquid solenoid valve status
Load and unload timer status
Water pump status
Provisions are included for: pumpdown at shutdown;
optional remote chilled water temperature reset and
two steps of demand load limiting from an external
building automation system. Unit alarm contacts are
standard.
The operating program is stored in non-volatile memo-
ry battery backed RAM to eliminate chiller failure due
to AC powered failure/battery discharge. Programmed
setpoints are retained in lithium battery-backed RTC
memory for 5 years minimum.
Communications
Native communication capability for BACnet
(MS/TP) and Modbus.
Optional communication available for N2 and
LON via eLink Gateway option.