Section 5: Technical data
Form QTC3-NM1
Issue date: 12/19/2023
55
QTC3 V Hz MCA Min. N/F
disc SW
Min. dual
elem. fuse
and CB
Max. dual
elem. CB
System 1
Compr. 1 Compr. 2 Compr. 3 Std. ow fans
RLA LRA RLA LRA RLA LRA Qty. FLA LRA
3040T
208 60 172 250 200 200 33.3 255 33.3 255 — — 2 7.6 44
230 60 171 250 200 200 33.3 255 33.3 255 — — 2 7.4 37
380 60 95 150 110 110 18.1 172.8 18.1 172.8 — — 2 4.5 23.1
460 60 81 100 90 90 15.4 140 15.4 140 — — 2 4 19
575 60 66 100 70 70 12.9 107.6 12.9 107.6 — — 2 2.9 15.3
3050T
208 60 225 400 250 250 45.9 335.5 45.9 335.5 — — 2 7.6 44
230 60 225 400 250 250 45.9 335.5 45.9 335.5 — — 2 7.4 37
380 60 119 150 125 125 23.8 183 23.8 183 — — 2 4.5 23.1
460 60 104 150 110 110 20.6 141 20.6 141 — — 2 4 19
575 60 73 100 80 80 14.5 109 14.5 109 — — 2 2.9 15.3
3055T
208 60 276 400 300 300 57.7 284 57.7 284
— —
2 7.6 44
230 60 275 400 300 300 57.7 330 57.7 330 — — 2 7.4 37
380 60 149 200 175 175 30.9 192 30.9 192 — — 2 4.5 23.1
460 60 130 200 150 150 26.9 180 26.9 180 — — 2 4 19
575 60 103 150 110 110 21.5 132 21.5 132
— —
2 2.9 15.3
3060T
208 60 306 400 350 350 57.7 284 57.7 249
— —
2 7.6 44
230 60 305 400 350 350 57.7 330 57.7 288 — — 2 7.4 37
380 60 170 250 200 200 30.9 192 30.9 139 — — 2 4.5 23.1
460 60 150 200 175 175 26.9 180 26.9 180 — — 2 4 19
575 60 112 150 125 125 21.5 132 21.5 132
— —
2 2.9 15.3
3070T
208 60 334 400 350 350 48.5 249 48.5 249 48.5 249 2 7.6 44
230 60 333 400 350 350 48.5 249 48.5 249 48.5 249 2 7.4 37
380 60 191 250 225 225 27.6 159 27.6 159 27.6 159 2 4.5 23.1
460 60 169 200 175 175 24.4 145 24.4 145 24.4 145 2 4 19
575 60 120 150 125 125 17.4 109 17.4 109 17.4 109 2 2.9 15.3
3075T
208 60 363 600 400 400 48.5 249 48.5 249 48.5 249 2 7.6 44
230 60 363 600 400 400 48.5 288 48.5 288 48.5 288 2 7.4 37
380 60 201 250 225 225 27.6 159 27.6 159 27.6 159 2 4.5 23.1
460 60 177 200 200 200 24.4 145 24.4 145 24.4 145 2 4 19
575 60 134 150 150 150 17.4 109 17.4 109 17.4 109 2 2.9 15.3
3079T
208 60 363 400 400 400 48.5 249 48.5 249 48.5 249 2 7.6 44
230 60 363 400 400 400 48.5 288 48.5 288 48.5 288 2 7.4 37
380 60 201 250 225 225 27.6 159 27.6 159 27.6 159 2 4.5 23.1
460 60 177 200 200 200 24.4 145 24.4 145 24.4 145 2 4 19
575 60 134 150 150 150 17.4 109 17.4 109 17.4 109 2 2.9 15.3
3085T
208 60 391 600 400 400 57.7 284 57.7 284 57.7 284 2 7.6 44
230 60 390 600 400 400 57.7 330 57.7 330 57.7 330 2 7.4 37
380 60 211 250 225 225 30.9 192 30.9 192 30.9 192 2 4.5 23.1
460 60 184 250 200 200 26.9 180 26.9 180 26.9 180 2 4 19
575 60 146 200 150 150 21.5 132 21.5 132 21.5 132 2 2.9 15.3
3090T
208 60 406 600 450 450 57.7 284 57.7 284 57.7 284 3 7.6 44
230 60 405 600 450 450 57.7 330 57.7 330 57.7 330 3 7.4 37
380 60 220 400 250 250 30.9 192 30.9 192 30.9 192 3 4.5 23.1
460 60 192 250 200 200 26.9 180 26.9 180 26.9 180 3 4 19
575 60 152 200 175 175 21.5 132 21.5 132 21.5 132 3 2.9 15.3
3095T
208 60 450 600 500 500 57.7 284 57.7 284 57.7 284 2 7.6 44
230 60 449 600 500 500 57.7 330 57.7 330 57.7 330 2 7.4 37
380 60 260 400 300 300 30.9 192 30.9 192 30.9 192 2 4.5 23.1
460 60 220 400 250 250 26.9 180 26.9 180 26.9 180 2 4 19
575 60 175 250 200 200 21.5 132 21.5 132 21.5 132 2 2.9 15.3
Table 12: Electrical data without pumps, R-454B