Bubble‐Up®JrInteractive™RadonRemovalSystem
12
StartUpProcedure
1. SettheredhandlesonthebypassvalvetotheServiceposition.
2. BeforeplugginginBubble‐Up®JrInteractive™,identifytheplug‐incords.Seefigure8.
3. Pluginthemetercontrolandwateralarmvalvecontrolpowercords.
4. Pushresetbuttononwateralarmvalve
controlfor3secondstoopenthemotorizedballvalve.
5. Plugintheyellowcordfirst.Theblowershouldstart,andthesolenoidvalveshouldopentobeginfillingthe
tank.
6. Asthewaterlevelinthetankrises,thefillfloatswitchwilltiltup.Thiswillstop
theblowerandclosethe
solenoidvalve.
7. Oncethetankisfull,plugintheblackpumpcontrolcord.
8. Ifthepumpdoesnotstartdeliveringwatertothehouse,itmaybenecessarytoprimethepump.(Normallyyou
willonlyhavetodothisonce,when
theunitisfirstin stalled.)Thepumpissuspendedbyapipeunderneaththe
pumpcontrol.Unscrewtheunionandmovethepumpcontrolofftotheside.Youmayneedtosiphonor
vacuumthewaterupthispipetoremovetheairfromthepumpandprimeit.
9. Oncetheairhasbeenremovedfromthepump,replacethepumpcontrolandtightentheunion.Pluginthe
pump.Ifthepumpdoesnotstartdeliveringwatertothehouse,repeattheprimingsequence.
10. Aftertheunitisoperating,runaradontestoftherawwater
andthefilteredwatertoensurethattheunitis
reducingradonlevelsinthewater.
RadonTestingNote:Itisimportanttoinstallanewsamplevalveorboilerdraininnewpipingsothattheradontesting
isnotinfluencedbyoldpiping.
11. Performthesix‐month
maintenanceprocedure, andfillouttheStart‐UpDatapageattheendofthismanual.
OperatingInstructions
OncetheBubble‐Up®JrInteractive™hasbeeninstalled,itshouldoperatewithverylittleattention.
NormalOperation
MainUnit
Theunitshouldnotneedanyoperatorattention.Whenwaterisusedinthehouse,the2.1gallonwaterexpansiontank
deliverswaterdemand.Whenthepressuredropstothe
setpressure,themechanicalpumpcontrolstartstheBubble‐
Up®JrInteractive™pumptodeliverwatertothehomeandrefillthe2.1gallonwaterexpansiontank.Whenthe
mechanicalpumpcontrolsensesnormalhouseholdpressure,themechanicalpumpcontrolshutstheBubble‐Up®Jr
Interactive™pumpoff.Asthe
waterlevelfallsintheBubble ‐Up®JrInteractive™maintank,thefloatswitchpowersthe
blowerandsolenoidtofilltheBubble‐Up®JrInteractive™tankwithtreatedwater.
LowWaterCut‐OutFloatSwitch
ThepumpwillautomaticallystopwhenthereislowwaterintheBubble‐Up
tank.Thepumpwillautomaticallyrestart
whenwaterisreplenished.
WaterAlarmValve
Thewateralarmvalveisinplaceforprotectionagainstleakingoroverflowingandwillnotoperateunlessoneofthese
thingshappens.Oncethewateralarmvalvecontrol,overflowalarmfloat,floorsensororterminalblocksenses
a
probleminthesystemthewateralarmvalvecontrolactivatesthemotorizedballvalveandshutsofftheincoming
water.Thewateralarmvalvecontrolwillalsosoundanalarmtoidentifythatthereisaproblem.