Bubble‐Up®JrInteractive™RadonRemovalSystem
29
At100%thresholdgallonstheredlightwillblink,andthemetercontrolwillbeepthreetimesevery15seconds
andoutput2willprovide12VAC30mapower.Thebeepcanbesilencedbypushinganybutton,andwill
remainsilentfortwodays.
To
resetthresholdandorbeepcontinuetoprogramming.
Programming
PressallthreebuttonsofthedisplaysimultaneouslytoenterProgramMode:
TheFlowbuttontogglestonextscreen,alsoactsastheEnterButton.
TheTotalFlowbuttontoggles thevaluesup.
ThePeakFlowbuttontogglesthevaluesdown.
ScreenOne:CLRMEMORYYES
NO.YEStoclearmemoryandresetthresholdorNOtocontinueprogramming.
NextScreen:SETPULSES
Shouldbefactorysetat83pulses.
NextScreen:SETTHRESHOLDTOTALYESorNO
ChooseYESorNOtousethresholdfunction.Thethresholdfunctionutilizestheyellowandred
displaylights,
alongwith12VACOutput2andaudiblealarm.
NextScreen:SETTHRESHOLDTOTAL(setgallonsfor12VACatconnection Opt2,.030ampsmax.)
Shouldbefactorysetat80whichtranslatesto80,000gallons.
80,000gallonsisanestimatedyearlyservicereminder
for4peopleusing50gallonsperdayeach.
Thisthresholdcanbesetforyourparticularapplicationatthistime.
YellowWarningLightwillflashat80%ofthresholdgallonsetting.
RedExpiredLightwilllightat90%ofthresholdgallonsetting.
At100%thresholdgallons
theredlightwillblink,andthemetercontrolwillbeepthreetimesevery15seconds
andoutput2willprovide12VAC30mapower.Thebeepcanbesilencedbypushinganybutton,andwill
remainsilentfortwodays.Toresetthresholdandalarmfollowthe
ClearMemoryinstructionsabove.
NextScreen:SETGAL/MIN(setGPMflowfor4‐20maconnection,J2+/‐)
Thereisnofactorysetting.
SetmaxflowGPMvaluefor20maflowsignal.
NextScreen:SETGAL1(setgallonsfor12VACoutputatconnectionOpt
1,.030ampsmax.)
Setbetween1to990gallonsforconnectionOpt1outputinterval.
YoucanalsosetatzeroforOpt1tobeusedasaflowswitchsensitiveat.5GPM.
NextScreen:SETMIN1(setminutesfor12VACconnection,Opt1minimum
runtime)
Setbetween.1to90minutesforconnectionOpt1outputminimumruntime.
ENDOFPROGRAMMING