MAINTENANCE INSTRUCTIONS
5. REGULATING THE BOILER
5.1 Parameter table
TYPE OF OPERATION
FUNCTION
1 Selects the type of boiler
01
Boiler with storage tank
B. w/storage tank Comfort (+7°C)
2 Selects the type of gas
3
Sets the central heating
temperature
Standard (30-80°C)
Reduced (25-40°C )
4
1
Selects pump mode during
heating phase
00
01
Standard ( 3’ pump overrun)
Permanent (pump runs
continuously)
5
Water hammer prevention
(Not applicable)
6 Central heating timer
00-90
(default = 36)
Delays the heating restart to
prevent frequent On/Offs,
Expressed in steps of 5 sec
(factory set at 36 x 5 = 180”)
7
Central heating pump
overrun timer
00-90
(default = 36)
The overrun timer can be modified.
Expressed in steps of 5 sec
(factory set at 36 x 5 = 180”)
8
D.H.W pump overrun timer
(Not applicable)
00-90
(default = 18)
The overrun timer can be modified.
Expressed in steps of 5 sec
(factory set at 18 x 5 = 90”)
9
Minimum gas pressure
setting
00-70 Factory set
10
Minimum central heating
output setting
00-80 Factory set
11
maximum central heating
Min gas – 99 Default = 99
Ignition sequence setting
13
D.H.W priority function (2
min delay on dhw function)
00
01
Off
On
15
2
Zone management board
activation
16
3
Telephone control activation
NOTES:
1 - Activate only for “heating only” boilers.
2 - If the heating system has more than one zone, an additional interface board (optional extra) must
be installed on the circuit board and parameter 15 set at 01.
3 - To install the telephone control, use non-polarised conductors connected to contact TA of the
terminal board in parallel with the remote control if fitted. Set the parameter 16 at 01.