EasyManua.ls Logo

Radiant RS 30 E - Page 27

Radiant RS 30 E
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MAINTENANCE INSTRUCTIONS
24
P
ARAMETER 4 CENTRAL HEATING PUMP
6. Use buttons
’ and ‘ to modify the value of the
parameter:
00 = standard (3” overrun)
01 = permanent (always running)
7. Press and release button ‘S’ to confirm. The parameter
number P04 will appear on the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
P
ARAMETER 5 WATER HAMMER PREVENTION
(Not applicable)
P
ARAMETER 6 CENTRAL HEATING TIMER
6. Use buttons
’ and ‘ to modify the value of the
parameter within the prescribed limits
00 = 0 x 5” = 0”
90 = 90 x 5” = 450” (7.5 min)
The default value is 36 = 180” = 3 min
7. Press and release button ‘S’ to confirm. The parameter
number P06 will appear on the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
P 04
S
S
S
S
S
S
00
01
P 05
36
P 06

Other manuals for Radiant RS 30 E

Related product manuals