MAINTENANCE INSTRUCTIONS
23
To enter the parameters menu, follow the previously described procedure (steps 1-5).
P
ARAMETER
1
T
YPE OF BOILER
6. Use buttons
’ and ‘ to modify the value of the
parameter:
00 = Instantaneous boiler
01 = Storage boiler;
02 = Storage boiler ‘comfort’ (+7°C).
7. Press and release button ‘S’ to confirm. The parameter
number P01 will appear on the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
P
ARAMETER 2 - GAS SUPPLY
6. Use buttons
’ and ‘ to modify the value of the
parameter:
00 = natural gas
01 = lpg
7. Press and release button ‘S’ to confirm. The parameter
number P02 will appear on the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
P
ARAMETER 3 CENTRAL HEATING TEMPERATURE
6. Use buttons
’ and ‘ to modify the value of the
parameter:
00 = standard (30 80°C)
01 = reduced (25 40 °C) for under-floor heating
7. Press and release button ‘S’ to confirm. The parameter
number P03 will appear on the display.
8. Switch off the appliance and switch it back on again to
render the new parameter operative.
P 01
S
S
S
S
S
S
00
01
P 02
01
P 03