TEMPERATURE CONTROL
34
Programming Parameters Eliwell IC902 Thermostat (On/Off models)
Level
Parameter
Unit
Minimum
Maximum
Raypak
Setting
CP
Set point differential (diF)
°C/°F
0.1
30
2
Set point Maximum (HSE)
°C/°F
-55
302
80
Set point Minimum (LSE)
°C/°F
-55
302
20
Heat / Cool mode (HC)
H/C
H
(Ont)
(Oft)
Delay, time relay on (dOn)
sec
0
250
0
Delay, time relay off (dOF)
min
0
250
0
(dbi)
min
0
250
0
Delay time at start up (OdO)
min
0
250
0
dis
Key pad lock (LOC)
y/n
n
Password (PA1)
num
0
250
0
View decimal point (ndt)
y/n
Calibration offset (CA1)
°C°F
-12
12
0
Units°C or°F (dro)
0/1
0
CnF
Probe type selection (HOO)
0/1
1
Device version (reL)
Reserved (tAB)
Fpr
Upload to copy card (UL)
Download from copy card (dL)