TEMPERATURE CONTROL
35
Programming Parameters Eliwell IC915 Thermostat (Hi/Lo models)
Parameter
Description
Range
Raypak
Setting
HC1
REGULATOR 1 (folder with “rE1label) Heat/Cool Mode. If set to H
the generic regulator actuates for hot operation. If set to C the generic
regulator actuates for cold operation
H/C
H
db1
Intervention 1 band see ON-OFF regulation diagram
0...30.0
1
dF1
diFferential. Relay 1 tripping differential. The regulator stops on
reaching the Setpoint value (as indicated by the adjustment probe),
and restarts at temperature value equal to the Setpoint 1 plus (o
minus depending on HC1) the value of the differential. see ON-OFF
regulation diagram
0.0...30.0
3
HS1
Higher SEt. Maximum possible setpoint 1 value.
LS1..HdL
95
LS1
Lower SEt. Minimum possible setpoint 1 value.
LdL..HS1
20
dn1
REGULATOR 1 PROTECTIVE DEVICE (folder with “rE1” label)
Delay time in activating the regulator relay after switch-on of
instrument.
0...250
1
do1
Delay after switch off. The indicated time must elapse between
switch-off of the regulator relay and the successive switch-on.
0...250
0
di1
Delay between switch-ons. The indicated time must elapse
between two successive switch-ons of the regulator.
0...250
0
dE1
Delay before switch-off. The indicated time must elapse between
switch-off request and the switch-off of the regulator.
PLEASE NOTE: for par. dn1, do1, di1, dE1 0= not active
0...250
0
On1
On time (regulator 1).
Regulator activation time in the event of faulty probe. If set to “1”
with OF1 at “0” the regulator is always on, while at OF1 >0 it
functions always in duty cycle mode.
0...250
0
OF1
OFF time (regulator 1). Regulator in disabled state time in the
event of a faulty probe. If set to “1” with On1 at “0 the regulator
is always off, while at On1 >0 it functions always in duty cycle
mode.
0...250
1
HC2
REGULATOR 2 (folder with “rE2” label)
Heat/Cool Mode. If set to H the generic regulator actuates for hot
operation. If set to C the generic regulator actuates for cold operation
H/C
H
db2
Intervention 2 band see ON-OFF regulation diagram
0...30.0
1
dF2
diFferential. Relay 1 tripping differential. The regulator stops on
reaching the Setpoint value (as indicated by the adjustment
probe), and restarts at temperature value equal to the Setpoint 1
plus (o minus depending on HC1) the value of the differential.
see ON-OFF regulation diagram
0.0...30.0
3
HS2
Higher SEt. Maximum possible setpoint 2 value.
LS1..HdL
95
LS2
Lower SEt. Minimum possible setpoint 2 value.
LdL..HS1
20