TEMPERATURE CONTROL
35
Programming Parameters – Eliwell IC915 Thermostat (Hi/Lo models)
REGULATOR 1 (folder with “rE1” label) Heat/Cool Mode. If set to H
the generic regulator actuates for hot operation. If set to C the generic
regulator actuates for cold operation
Intervention 1 band see ON-OFF regulation diagram
diFferential. Relay 1 tripping differential. The regulator stops on
reaching the Setpoint value (as indicated by the adjustment probe),
and restarts at temperature value equal to the Setpoint 1 plus (o
minus depending on HC1) the value of the differential. see ON-OFF
regulation diagram
Higher SEt. Maximum possible setpoint 1 value.
Lower SEt. Minimum possible setpoint 1 value.
REGULATOR 1 PROTECTIVE DEVICE (folder with “rE1” label)
Delay time in activating the regulator relay after switch-on of
instrument.
Delay after switch off. The indicated time must elapse between
switch-off of the regulator relay and the successive switch-on.
Delay between switch-ons. The indicated time must elapse
between two successive switch-ons of the regulator.
Delay before switch-off. The indicated time must elapse between
switch-off request and the switch-off of the regulator.
PLEASE NOTE: for par. dn1, do1, di1, dE1 0= not active
On time (regulator 1).
Regulator activation time in the event of faulty probe. If set to “1”
with OF1 at “0” the regulator is always on, while at OF1 >0 it
functions always in duty cycle mode.
OFF time (regulator 1). Regulator in disabled state time in the
event of a faulty probe. If set to “1” with On1 at “0” the regulator
is always off, while at On1 >0 it functions always in duty cycle
mode.
REGULATOR 2 (folder with “rE2” label)
Heat/Cool Mode. If set to H the generic regulator actuates for hot
operation. If set to C the generic regulator actuates for cold operation
Intervention 2 band see ON-OFF regulation diagram
diFferential. Relay 1 tripping differential. The regulator stops on
reaching the Setpoint value (as indicated by the adjustment
probe), and restarts at temperature value equal to the Setpoint 1
plus (o minus depending on HC1) the value of the differential.
see ON-OFF regulation diagram
Higher SEt. Maximum possible setpoint 2 value.
Lower SEt. Minimum possible setpoint 2 value.