EasyManuals Logo

RBI FUTERA XLF Series User Manual

RBI FUTERA XLF Series
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #109 background imageLoading...
Page #109 background image
MODBUS COMMUNICATIONS HeatNet Control V3
Page 109
Figure 65 MODBUS BoilerStatus Flags
Bit
Description
Valid Values/Range
12
System Pump
0 = off, 1 = on
13
Combustion Air Damper
0 = off, 1 = on
14
Master Boiler
0 = Member, 1 = Master
15
Boiler Detected (at this address)
0 = not detected, 1 = detected
Figure 66 MODBUS BoilerStatus2 Flags
Bit
Description
Valid Values/Range
0
Disabled
0 = enabled, 1 = disabled
1
Heat Demand
0 = no demand, 1 = demand (1)
2
Alarm
0 = ok, 1 = alarm
3
Failed
0 = ok, 1 = failed
4
Member Error
0 = ok, 1 = error
5
Boiler Running
0 = off, 1 = running
6
Pump Running
0 = off, 1 = running
7
Spare 3 Interlock
0 = open, 1 = closed
8
LWCO Interlock
0 = open, 1 = closed
9
VFD Interlock
0 = open, 1 = closed
10
Gas Prove Interlock
0 = open, 1 = closed
11
Spare 4 Interlock
0 = open, 1 = closed
12
Operator Interlock
0 = open, 1 = closed
13
Water Prove (Flow) Interlock
0 = open, 1 = closed
14
UV Sensor Air Prove Interlock
0 = open, 1 = closed
15
Main Valve
0 = closed, 1 = open
This BoilerStatus2 Heat Demand Flag is a combination of the Heat Demand input and the Modbus Heat Demand (40001).
Figure 67 MODBUS BoilerStatus3 Flags
Bit
Bit
Bit
0
AA High Fire
0 = off, 1 = on
1
Heat Demand (Local Override)
0 = off, 1 = on (1)
2
4-20mA Remote Enable
0 = off, 1 = on
3
Outdoor Air Reset Override
0 = off, 1 = on
4
T1
0 = off, 1 = on
5
T2
0 = off, 1 = on

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RBI FUTERA XLF Series and is the answer not in the manual?

RBI FUTERA XLF Series Specifications

General IconGeneral
BrandRBI
ModelFUTERA XLF Series
CategoryController
LanguageEnglish

Related product manuals