EasyManua.ls Logo

RBI HEATNET 3.0 Torus Series - Page 37

RBI HEATNET 3.0 Torus Series
136 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CONTROL METHODS HeatNet Control V3
Page 37
DHW Method 2 W/Pumps Quick Start Settings
DHW METHOD 2: Combination DHW and Space Heating Using a MASTER Boiler and
Member Boiler(s) Utilizing DHW Pumps
Master (Space Heating Only W/Pumps)
Settings
Master Type
HeatNet Address
DHW Use Sensor
Combustion Air Damper
Combination
Automatic
Yes
Off
Inputs
Local/Remote
OR/OVR
Header Sensor
System Return
DHW Sensor
Local
Jumper
Yes
Optional
Yes - Tank
Outputs
System Pump On
Local Pump
When Boiler Enabled
When Boiler Running
Member 2 (Space Heating Or DHW, Failsafe Space Heating W/Pumps)
Settings
HeatNet Address
DHW Boiler Mode
DHW Local Pump Off
Combustion Air Damper
HeatNet Failsafe
2
Combination
Yes
Off
On
Inputs
Local/Remote
JPS1 Jumper must be cut to service DHW
Remote
Outputs
System Pump On
Local Pump On
DHW Pump On
Failsafe Heating
When Boiler Running
DHW Call
Member 3 (Space Heating Or DHW, Failsafe Space Heating and DHW W/Pumps)
Settings
HeatNet Address
DHW Boiler Mode
DHW Local Pump Off
Combustion Air Damper
3
Combination
Yes
Off
HeatNet Failsafe
DHW Use Sensor
System Pump Priority
On
Yes
Yes
Inputs
Local/Remote
OR/OVR
DHW Sensor
JPS1 Jumper must be cut to service
DHW
Remote
Jumper
Yes - Tank
Outputs
System Pump On
Local Pump On
DHW Pump On
Failsafe Heating
When Boiler Running
DHW Call

Table of Contents

Related product manuals