EasyManua.ls Logo

RBI HEATNET 3.0 Torus Series - Using the 4-20 mA Input

RBI HEATNET 3.0 Torus Series
136 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OPTIONAL FEATURES HeatNet Control V3
Page 60
Using the 4-20mA input (OPTIO NAL)
The 4-20mA input is designed to operate per the ISA-50.1
standard. It will support Type 2, Type 3, and Type 4
Transmitter/Receiver circuits.
The Type 2 and Type 3 circuit may use the supplied +24VDC
and 24VDC RET connections (J10B) to power a remote
transmitter. The ma terminal will need to have a jumper
connected to the adjacent 24VDC RET terminal to reference
the signal ground.
With the type 4 configuration, multiple boilers (up to 5), may
be connected in series using the ma +ma ma +ma scheme
(no jumper to 24VDC RET). This allows one 4-20mA
transmitter to control multiple boilers. A free-floating 250-
ohm resistor is viewed by the BMS (or external control’s) 4-
20mA transmitter across the + and 4-20mA terminals with
this method.
Example: 420mA connections
420mA enable connection
Closing this contact enables
the 4-20mA/0-10VDC input
The 4-20mA input uses a 250-ohm sense resistor to convert
the current to a voltage from 1 to 5VDC for the control to use.
For this reason, a 1-5VDC control voltage may also be used
across the 4-20mA +/- input, but it still needs to supply the
necessary current, i.e., 20mA. This resistor is located on the
bottom side of the control board. When a 4.02mA signal is
sensed, the boiler will initiate a start sequence and fire the
boiler at its minimum setting if the REMOTE ENABLE input
is closed. This is typically 25% of the boilers output (4:1
turndown).
If the dip switch S6 is set to the 0-10VDC position (UP) See:
Figure 51, the 4-20mA input will accept a 0-10VDC signal.
The channel will also need to be setup in the menu:
SETTINGS: 4-20mA INPUT: CHANNEL MODE. The
operating range will be from 2-10VDC or twice what was
previously stated for the 1-5VDC functionality. To convert a
0-10VDC signal to mA, divide by 2510 (ohms).
NOTE: Due to the inability of control voltage methods (1-5,
2-10VDC) to reject noise and compensate for line loss, the
use of the 4-20mA control current is recommended. The
control voltage methods may be less expensive but are the
least stable. If using a 0-10VDC control signal, a source
current of 5mA is required.
If using a remote panel with a relay and a 4-20mA transmitter
for operation, connect the 4-20mA transmitter output from the
remote panel to the member boilers using the floating 250-
ohm method (type 4). The relay contacts on the remote panel
will then be connected to the associated 4-20mA REMOTE
ENABLE inputs on the associated boiler(s).

Table of Contents

Related product manuals