CONTROL METHODS HeatNet Control V3
Page 55
DHW Method 5b Quick Start Settings
DHW METHOD 5b: Local Tank Heating using a Hybrid Sensor
Master
Settings
Master Type
HeatNet Address
Combustion Air Damper
Automatic
Automatic
Off
Inputs
Local/Remote
Header Sensor
System Return
Local
Yes
Optional
Outputs
System Pump On
Local Pump On
When Boiler Enabled
When Boiler Running
Member 2
Settings
HeatNet Address
DHW Boiler Mode
Combustion Air Damper
2
Local
Off
DHW Use Sensor
Hybrid Sensor
DHW Local Pump Off
No
Supply
Yes
Inputs
Local/Remote
OR OVR
JPS1 Jumper must be cut to service DHW
Remote
Tank Aquastat
Outputs
Local Pump On
DHW Pump On
Space Heating Call
DHW Call
Member 3
Settings
HeatNet Address
DHW Boiler Mode
Combustion Air Damper
3
Local
Off
DHW Use Sensor
Hybrid Sensor
DHW Local Pump Off
No
DHW
Yes
Inputs
Local/Remote
OR OVR
JPS1 Jumper must be cut to service DHW
Remote
Tank Aquastat
Outputs
Local Pump On
DHW Pump On
Space Heating Call
DHW Call

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RBI HEATNET 3.0 Torus Series and is the answer not in the manual?

RBI HEATNET 3.0 Torus Series Specifications

General IconGeneral
BrandRBI
ModelHEATNET 3.0 Torus Series
CategoryBoiler
LanguageEnglish

Related product manuals