-2-
Bulletin No. CR1000-A Effective 2017-09-26
Drawing No. LP1019
1. POWER REQUIREMENTS:
Must use a Class 2 circuit according to National Electrical Code (NEC),
NFPA-70 or Canadian Electrical Code (CEC), Part I, C22.1 or a
Limited Power Supply (LPS) according to IEC 60950-1 or Limited-
energy circuit according to IEC 61010-1.
Power connection via removable three position terminal block.
Supply Voltage: 24 VDC ±20%, Class 2
2. BATTERY: Lithium coin cell. Typical lifetime of 5 years, nominal.
To maintain UL rating, replacement battery must be: Red Lion CRA000
BT3V0 00000, Rayovac BR1225X-BA or Panasonic BR1225A/BN.
3. LCD DISPLAY:
4. TOUCHSCREEN: Four-wire resistive analog
5. MEMORY:
On Board User Memory: 512 Mbyte of non-volatile Flash memory.
Memory Card: SD slot accepts standard capacity cards up to 16 GB.
6. COMMUNICATION CAPABILITIES:
USB Device Port: Isolated and adheres to USB specification 2.0 full
speed only using Type B connection.
USB DEVICE PORT IS FOR
SYSTEM SET-UP AND DIAGNOSTICS AND IS NOT INTENDED FOR
PERMANENT CONNECTION.
Serial Ports (2): Ports are individually isolated. Format and Baud
Rates for each port are individually software programmable up to
115,200 baud.
Port to Port Isolation: 3000 Vrms for 1 minute.
Signal Isolation: 500 V.
Ethernet Port: 10 BASE-T / 100 BASE-TX
RJ45 jack is wired as a NIC (Network Interface Card).
Isolation from Ethernet network to operator interface: 1500 Vrms
7. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: -10 to 50 °C
Storage Temperature Range: -20 to 70 °C
Vibration to IEC 68-2-6: Operational 5-500 Hz, 2 g
Shock to IEC 68-2-27: Operational 30 g
Operating and Storage Humidity: 0 to 85% max. RH non-condensing
Altitude: Up to 2000 meters
Installation Category II, Pollution Degree 2 as defined in IEC/EN 60664-1.
8. CERTIFICATIONS AND COMPLIANCES:
CE Approved
Immunity: IEC/EN 61000-6-2 for Industrial Locations
Emissions: IEC/EN 61000-6-4 for Industrial Locations; CISPR 11 Class A
IEC/EN 61010-1
RoHS Compliant
UL Listed: File #E302106
Type 4X Indoor / IP66 Enclosure rating (Face only)
9. CONNECTIONS: High compression cage-clamp terminal block
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage Capacity: 12 to 24 AWG (3.31 to 0.20 mm
2
) copper wire
Torque: 4.4-5.3 inch-lbs (0.5-0.6 N-m)
10. CONSTRUCTION: Polycarbonate enclosure with Type 4X/IP66 rating
when correctly fitted per the mounting instructions provided.
Protection against mechanical impact up to 5 Joule, IK08 per IEC 62262.
11. MOUNTING REQUIREMENTS: Maximum panel thickness is 0.25"
(6.35 mm) with included stiffener plate, or 0.375" (9.53 mm) without
plate. For
NEMA 4X / IP66 sealing, a panel with a minimum
thickness of
0.06" (1.52 mm) is recommended.
Recommended mounting screw torque: 4.0 lbf-in (0.45 Nm).
Maximum Mounting Screw Torque: 5.0 lbf-in (0.57 Nm)
12. WEIGHT: Unit weight with stiffener plate and clips
CR1000 04: 15 oz (425 g)
CR1000 07: 1.91 lb (868 g)
CR1000 10: 3.08 lb (1.395 Kg)
@ 24 VDC 4-INCH 7-INCH 10-INCH
Typical Power: 3.9 W 5.3 W 8.3 W
Max Power: 5.0 W 6.2 W 9.0 W
4-INCH 7-INCH 10-INCH
TYPE TFT TFT TFT
COLORS 16M 16M 16M
PIXELS 480 x 272 800 X 480 800 X 600
BRIGHTNESS
500 cd/m
2
430 cd/m
2
400 cd/m
2
BACKLIGHT TYPE LED LED LED
BACKLIGHT LIFE 30K HR TYP. 50K HR TYP. 50K HR TYP.
DIMENSIONSINinches(mm)
4 inch
4.12
(104.69)
5.14 (130.65)
4.62
(117.48)
5.65 (143.51)
3.62
(92.08)
1.50
(38.1)
THIS VIEW SHOWN WITH MOUNTING PLATE AND BRACKETS
CR100004
7 inch
5.43
(138.02)
7.63 (193.98)
5.80
(147.32)
8.00 (203.2)
4.80
(121.92)
2.00
(50.8)
THIS VIEW SHOWN WITH MOUNTING PLATE AND BRACKETS
CR100007
SPECIFICATIONS

Related product manuals