-3-
Effective 2017-09-26 Bulletin No. CR1000-A
Drawing No. LP1019
INSTALLINGANDPOWERINGTHECR1000
10.4 inch
THIS VIEW SHOWN
WITH MOUNTING PLATE
AND BRACKETS
10.78 (273.73)
11.14 (282.96)
8.87
(225.29)
8.50
(215.99)
7.87
(199.9)
2.00
(50.8)
CR100010
MOUNTINGINSTRUCTIONS
This operator interface is designed for through-panel mounting. The
mounting surface should have a minimum thickness of 0.06” (1.53 mm)
and maximum thickness of 0.375” (9.53 mm). There should be a minimum
of 4” clearance behind the panel for unit installation. Allow a minimum of
2.5“ below the bottom connectors for communication cables. Cut the
mounting hole per the dimensions shown in the diagram. Care should be
taken to remove any loose material from the mounting cut-out to prevent
that material from falling into the operator interface during installation.
If installing the unit in an enclosure, follow the table below for minimum
enclosure size to allow for proper ventilation and cabling to meet UL
requirements. Consider heat produced by other devices in the enclosure.
PART NUMBER WIDTH HEIGHT DEPTH
CR1000 04000 00210 10.5 inch 12.5 inch 6.25 inch
CR1000 07000 00210 10.5 inch 12.5 inch 6.25 inch
CR1000 10000 00210 12.55 inch 14.55 inch 8.31 inch
10.4 INCH PANEL CUT-OUT
4 INCH PANEL CUT-OUT
7 INCH PANEL CUT-OUT
Must meet hole tolerance specification for
full NEMA4X and IP66 ingress protection.
4.69
(119.13)
3.66
(92.96)
4.87
(123.7)
7.93
(201.42)
10.20 (259.08)
7.06 (179.32)
R
0.10
(2.54)
R
0.08
(2.03)
R
0.10
(2.54)
ALL TOLERANCES +/-0.03" (+/-0.762 mm)
Follow these steps to install the unit.
1. Make sure the bezel gasket is properly in place.
2. Place the unit into the front of the panel cutout.
3. Install stiffener plate over unit on the inside of the panel. This ensures
the mounting surface is stiff enough for a proper seal. The plate is
required to meet NEMA 4X and IP66.
4. Insert clamps into the slots provided on the sides (CR100004) or top
and bottom (CR100007 and CR100010) of the unit.
5. Make sure the clamp’s screw sits in the “U” shaped feature located on
the stiffener plate. This will prevent the screw from “walking”. Tighten
the clamping screws in an even pattern until the unit is secured in the
panel. To seal to Type 4X/IP66 specifications, all supplied mounting
clamps must be used and be torqued to at least 4.0 lbf-in (0.45 Nm).
The maximum torque is 5.0 lbf-in (0.57 Nm). CAUTION: DO NOT
OVERTIGHTEN THE CLAMPS. The panel must not flex more than
0.010" for proper sealing. The safety of any system incorporating the
equipment is the responsibility of the assembler of the system.

Related product manuals