-6-
Bulletin No. CR1000-A Effective 2017-09-26
Drawing No. LP1019
RS232/RS422/485COMMSPORT
The Port B of the CR1000 can be used as a RS232 or RS422/485 port.
There is a separate RJ connector for each option. In addition, the RS485/
422 option can be configured to act as either RS485 or RS422. Each
serial port has a pair of LEDs to indicate transmit and receive activity.
Note: All Red Lion devices connect A to A and B to B. Refer to
www.redlion.net for additional information.
ExamplesofRS4852WireConnections
DH485COMMUNICATIONS
The CR1000’s RS422/485 COMMS port can also be used for Allen
Bradley DH485 communications.
WARNING: DO NOT use a standard DH485 cable to connect this port to
Allen Bradley equipment. A cable and wiring diagram are available
from Red Lion at www.redlion.net/cables-drivers
.
CRIMSON
®
SOFTWARE
Crimson software is available as a no charge download from Red
Lion’s website. The latest version of the software is always available from
the website, and updating your copy is free.
DISPLAY
This operator interface uses a liquid crystal display (LCD) for
displaying text and graphics. The display utilizes an LED backlight for
lighting the display. The backlight can be dimmed for low light conditions.
The LED backlight has a limited lifetime. Backlight lifetime is based
upon the amount of time the display is turned on at full intensity. Turning
the backlight off when the display is not in use can extend the lifetime of
your backlight. This can be accomplished through the Crimson software
when configuring your unit.
TX
5V
8
1
7
2
TxB
TxA
130K
130K
5
TxEN (OC)
RX
130K
5V
130K
RxB
4
RxA
3
COMM
6
RS422/485 4-WIRE
CONNECTIONS
RS485 2-WIRE
CONNECTIONS
TxEN (OC)
TX/RX
130K
5
TxA
2
8
130K
5V
7
1
TxB
6 COMM
FRONTPANELLEDS
There are three front panel LEDs that can be configured using Crimson.
Shown below is the default status of the LEDs.
FACTORYRESETBUTTON
The factory reset button located in the lower right area of the rear panel
can be used to access the system menu. Refer to Crimson 3 System
Menu Technical Note at www.redlion.net/TNIA37
for access procedure
and available options.
LED INDICATION
GREEN ()
STEADY Unit is powered.
BLUE ()
FLASHING
Unit is in the boot loader
OFF No SD card is present.
STEADY Valid SD card present.
FLASHING RAPIDLY SD card being checked.
FLICKERING SD card accessed.
FLASHING SLOWLY Incorrectly formatted SD card present.
RED ()
FLASHING Data tag is in an alarm active state.
STEADY Data tag is in an alarm accepted state.
SOFTWARE/UNITOPERATION
CR1000 to Red Lion RJ11
HMI:RJ45 Name RLC:RJ11 Name
5TxEN 2 TxEN
6COMM 3 COMM
1TxB 5 B-
2TxA 4 A+
CR1000 to Modular Controller
HMI Name
Modular
Controller
Name
1,4 TxB 1,4 TxB
4,1 RxB 4,1 RxB
2,3 TxA 2,3 TxA
3,2 RxA 3,2 RxA
5TxEN 5 TxEN
6COMM 6 COMM
7TxB 7 TxB
8TxA 8 TxA