-7-
Effective 2017-09-26 Bulletin No. CR1000-A
Drawing No. LP1019
TOUCHSCREEN
This operator interface utilizes a resistive analog touchscreen for user
input. The unit will only produce an audible tone (beep) when a touch on
an active touchscreen cell is sensed. The touchscreen is fully functional
as soon as the operator interface is initialized, and can be operated with
gloved hands.
TROUBLESHOOTINGYOURCR1000
If for any reason you have trouble operating, connecting, or simply
have questions concerning your new CR1000 unit, contact Red Lion’s
technical support.
Email: support@redlion.net
Website: www.redlion.net
Inside US: +1 (877) 432-9908
Outside US: +1 (717) 767-6511
BATTERY&TIMEKEEPING
A battery is used to keep time when the unit is without power. The
battery of a CR1000 unit does not affect the unit’s memory, all
configurations and data is stored in non-volatile memory.
ChangingtheBattery
To change the battery of a CR1000, first remove power to the unit.
Remove the SD card if one is installed. Insert a small screwdriver into the
slot provided on the battery holder and pry the battery holder with battery
out of the unit. Remove the old battery from the plastic holder and replace
it with a new battery. Make sure the orientation of the battery is correct
and as shown in the diagram.
Re-install the battery holder with battery into the CR1000 unit. Using
Crimson or the unit’s keypad, enter the correct time and date.
CAUTION: Lithium battery. Danger of explosion if battery is
incorrectly replaced. Replace only with the same or equivalent
type recommended by the manufacturer.
Please note that the old battery must be disposed of in a
manner that complies with your local waste regulations. The
battery must not be disposed of in fire, or in a manner whereby
it may be damaged and its contents could come into contact
with human skin.
To maintain UL rating, battery must
be replaced with one listed in the
Specifications.