-44-
Drawing No. LP0932 Released 2018-01-12
REGISTER
(4x)
REGISTER NAME LOW LIMIT HIGH LIMIT
FACTORY
SETTING
ACCESS COMMENTS
35 Derivative time 1 0 9999 30 Read/Write 1 = 1 second
36 Integration default 1 0 1000 0 Read/Write 1 = 0.1 %
37 Proportional band 2 1
999(.9)° or
9999 (process)
700 Read/Write 1 = 1 Display unit
38 Integral time 2 0 9999 120 Read/Write 1 = 1 second
39 Derivative time 2 0 9999 30 Read/Write 1 = 1 second
40 Integration default 2 0 1000 0 Read/Write 1 = 0.1 %
41 Output Power Offset 0 1000 500 Read/Write 1 = 0.1 % output power
INPUT PARAMETERS
51 Input Type 0 19 1 Read/Write
0 = tc-K 1 = tc-J 2 = tc-t 3 = tc-E 4 = tc-N
5 = tc-r 6 = tc-S 7 = tc-b 8 = tc-L 9 = tc-U
10 = tc-txk 11 = r392 12 = r385 13 = n1
14 = cu50 15 = 5v 16 = 10v 17 = 0-20mA
18 = 4-20mA 19 = 0.05v
52 Temperature Scale 0 1 0 Read/Write 0 = °F, 1 = °C
53 Decimal Resolution 0 3 1 Read/Write
0 = 0 (No decimal place) 1 = 0.0, 2 = 0.00,
3 = 0.000. Temperature inputs are limited to 1 decimal
point except for the thermocouple B,S,R types, which
display in whole units only (0)
54 Digital Filtering 0 50 8 Read/Write 0 = least, 50 = most
55 Input Filter Band 0
25(.0)° or
250 (process)
10 Read/Write 1 = 1 Display unit
56 Shift/Offset
-99(.9)° or
999 (process)
99(.9)° or
999 (process)
0 Read/Write 1 = 1 Display unit
57 Display Value Scaling Point 1 -999 9999 0 Read/Write
1 = 1 Display unit; Value associated with lower range
of input signal (0V, 0mA or 4mA)
58 Display Value Scaling Point 2 -999 9999 1000 Read/Write
1 = 1 Display unit; Value associated with upper limit
of input signal (50mV, 5V, 10V, or 20mA)
59 Setpoint Low Limit
depending on
sensor type
Upper-limit of
temperature range
-1480 Read/Write 1 = 1 Display unit
60 Setpoint High Limit
Lower-limit of
temperature
range
Depends on
sensor type
21920 Read/Write 1 = 1 Display unit
61 Cold Junction Compensation 0 1 0 Read/Write 0 = On, 1 = OFF
62 User Input 1 Function 0 11 0 Read/Write
0 = NONE, 1 = r-S, 2 = SPSL, 3 - trnF, 4 - PLOC,
5 - ILOC, 6 - SPrP, 7 - ALrS, 8 - Alr, 9 - A2rS, 10 -
A3rS, 11 - PStr, 12 - PStP, 13 - PAdv, 14 - PrrH
63 User Input 2 Function 0 11 0 Read/Write
0 = NONE, 1 = r-S, 2 = SPSL, 3 - trnF, 4 - PLOC,
5 - ILOC, 6 - SPrP, 7 - ALrS, 8 - Alr, 9 - A2rS, 10 -
A3rS, 11 - PStr, 12 - PStP, 13 - PAdv, 14 - PrrH
64 F1 Key Function 0 8 0 Read/Write
0 = NONE, 1 = r-S, 2 = SPSL, 3 - trnF, 4 - ALrS,
5 - Alr, 6 - A2rS, 7 - A3rS, 8 - PStr, 9 - PStP,
10 - PAdv, 11 - PrrH
65 F2 Key Function 0 8 0 Read/Write
0 = NONE, 1 = r-S, 2 = SPSL, 3 - trnF, 4 - ALrS,
5 - Alr, 6 - A2rS, 7 - A3rS, 8 - PStr, 9 - PStP,
10 - PAdv, 11 - PrrH
66 Remote Input Type 0 4 4 Read/Write
0 = 0-5V, 1 = 1-5V, 2 = 0-10V, 3 = 0-20mA,
4 = 4-20mA
67 Remote Input Low Display -999 0 Read/Write
68 Remote Input High Display 9999 1000 Read/Write
69 Remote Input Ratio 1 9999 1 Read/Write
70 Remote Input Bias -1999 9999 0 Read/Write
OUTPUT PARAMETERS
71 Analog Output Assignment 0 3 3 Read/Write 0 = OP1, 1 = OP2, 2 = SP, 3 = Inpt (PV)
72 Analog Output Update Time 10 Read/Write
73 Analog Low Scaling -1999 9999 0 Read/Write
74 Analog High Scaling -1999 9999 1000 Read/Write