The dimensions of the opening that gives access to the dangerous area and
the calculated safety distance help in the choice of the right model.
These characteristics must be compared to the scanning
These characteristics must be compared to the scanningThese characteristics must be compared to the scanning
These characteristics must be compared to the scanning
distance, the protection height and the different resolu
distance, the protection height and the different resoludistance, the protection height and the different resolu
distance, the protection height and the different resolu-
--
-
tions of the ARGOLUX AS system.
tions of the ARGOLUX AS system.tions of the ARGOLUX AS system.
tions of the ARGOLUX AS system.
The ARGOLUX AS light curtain should protected against moving equi-
pment, oil, dust, etc.
The control unit AU S3 should be installed in an enclosure at
The control unit AU S3 should be installed in an enclosure atThe control unit AU S3 should be installed in an enclosure at
The control unit AU S3 should be installed in an enclosure at
least IP54.
least IP54.least IP54.
least IP54.
Before installing the safety barrier, the following conditions should be
observed:
Ambient temperature should be compatible with the specified
operating temperature.
The emitter and the receiver should be protected against excessive
light source intensity (greater than the specified ambient light
immunity).
Fog, rain, smoke or dust may influence optoelectronic devices.
Therefore, we recommend to apply a correction value Fc to the
specified nominal scanning range in order to guarantee a correct
operation of the system:
Pu = Pm x Fc
Pu = Pm x FcPu = Pm x Fc
Pu = Pm x Fc
Pu: maximum scanning range in meters.
Pm: nominal scanning range in meters for a clear environment.
The following table shows the recommended correction values.
If sudden temperature variations are foreseen, proper measures
should be taken to avoid condensation accumulation on lens.
Excessive accumulation could generated unexpected alarm.
ENVIRONMENT
ENVIRONMENTENVIRONMENT
ENVIRONMENT
CORRECTION VALUE
CORRECTION VALUECORRECTION VALUE
CORRECTION VALUE
Fc
Fog 0,25
Vapour 0,50
Dust 0,50
Thick smoke 0,25
!
!
16
1616
16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Reer ARGOLUX AS Series and is the answer not in the manual?

Reer ARGOLUX AS Series Specifications

General IconGeneral
BrandReer
ModelARGOLUX AS Series
CategorySafety Equipment
LanguageEnglish

Related product manuals