InstallationIndications, functions and optionsMessages Commissioning Operation and function
Only conrm the security enquiry if you are
sure that you wish to change the system selec-
tion.
Security enquiry:
Î In order to conrm the security enquiry, press
button 3.
5. Maximum store temperature
Î Adjust the desired maximum store temperature.
S MX / S1MX / S2MX
Maximum store temperature
Adjustment range: 4 … 95 °C [40 … 200 °F]
Arr 10: 4 … 90 °C [40 … 190 °F]
Factory setting: 75 °C [167 °F]
Note
The controller is also equipped with a non-ad-
justable emergency shutdown, deactivating
the system if the store reaches 95 °C [200 °F].
6. Pump control type
Î Adjust the pump control type.
PUM1 / PUM2
Pump control type
Selection: OnOF, PULS, PSOL, PHEA
Factory setting: PSOL
The following types can be selected:
Adjustment for standard pump without speed control
OnOF (pump on / pump off)
Adjustment for standard pump with speed control
PULS (burst control via semiconductor relay)
Adjustment for high-efciency pump (HE pump)
PSOL (PWM prole for a HE solar pump)
PHEA (PWM prole for a HE heating pump)
7. Minimum speed
Î Adjust the minimum speed for the corresponding
pump.
nMN, n1MN, n2MN
Minimum speed
Adjustment range: (10) 30 … 100 %
Factory setting: 30 %
Note
The pump speed must be set to 100 % when
auxiliary relays or valves are connected.
8. Maximum speed
Î Adjust the maximum speed for the corresponding
pump.
nMX, n1MX, n2MX
Maximum speed
Adjustment range: (10) 30 … 100 %
Factory setting: 100 %
Note
The pump speed must be set to 100 % when
auxiliary relays or valves are connected.
CommissioningCommissioning