Point of emissions
Assessment level in accordance
with TA noise
days in dB(A) nights in dB(A)
Industrial areas 70 70
Commercial areas 65 50
Core areas, village areas and mixed zones 60 45
General residential areas and small housing estates 55 40
Exclusively residential areas 50 35
Spa areas, hospitals and mental institutions 45 35
Isolated noise peaks of short duration may not exceed 30 dB(A) during the day and 20 dB(A) at night.
Definition of the Danger Area
WARNING!
Access to the unit is only permitted for author-
ised and trained persons. If unauthorised per-
sons can approach the danger areas, these
areas must be identified with corresponding
signs, barriers, etc.
n The external danger area surrounds the equip-
ment up to a distance of 2 m, measured in all
directions from the unit housing.
n The external danger area on-site can differ as
a result of the setup. The specialist company
performing the installation work bears the
responsibility for this.
n The internal danger area is located inside the
machine and can only be reached with the use
of an appropriate tool. Access is prohibited for
unauthorised persons!