Error E3: Indoor fan speed has been out of control
Shut off the power
supply and turn it on
5 seconds later. Is it
still displaying the
error code?
The unit operates normally.
Shut off the power
sopply, rotate the
cross fan by hand.
Does it rotate prop-
erly?
Disassembly the connection between fan
and motor, check if the bearing is normal?
Check the wires of
fan motor. Are all
the connections
good?
Correct the connec-
tions.
Replace indoor fan
motor.
Replace the
bearing.
Check the resist-
ance value of indoor
fan motor, is it
normal?
Replace indoor fan
motor.
Replace indoor
PCB.
Error E3-E4 and F1-F3 : sensor error
Check the connections between temperature
sensor and PCB. Are the connections good?
Correct the connetions.
Check the resistance of the sensor. Use the
resistance-sensor. Does the Resistance of the
sensor with the value in the table match?
Replace the sensor.
Replace indoor or outdoor PCB.