Resistance values of the sensors T1, T2, T3 and T4
Temperature
(°C)
5 10 15 20 25 30 40 50 60
Resistance value
(kW)
26,9 20,7 16,1 12,6 10,0 8,0 5,2 3,5 2,4
Resistance value of the sensor T5
Temperature
(°C)
5 15 25 35 60 70 80 90 100
Resistance value
(kW)
141,6 88 56,1 36,6 13,8 9,7 6,9 5,0 3,7
Temperature / resistance
W
T
T5
T1, T2, T3, T4
Fig. 54: Temperature / resistance
W: Resistance (kW)
T: Temperature (°C)