Data specific to indoor unit IT
RVT 262 RVT 352 RVT 522 RVT 682
Dimensions: H/W/D mm 280/750/198 280/835/198 315/990/218 340/1186/258
Weight kg 7 9 12 16
EDP no. 1623109 1623119 1623129 1623139
Data specific to outdoor unit AT
RVT 262 RVT 352 RVT 522 RVT 682
Power supply
V/Ph/
Hz
230 / 1~ / 50
Operating range, cooling °C +5 bis +50
Operating range, heating °C -20 to +34
Air flow rate, max. m³/h 1800 1800 2200 2700
Enclosure class IP 24
Sound power max. dB (A) 59 63 61 67
Sound pressure level
5)
dB (A) 48 52 50 56
Refrigerant
6)
R 410A
Refrigerant, basic capacity kg 1,1 1,1 1,25 2,25
Max. operating pressure kPa 4200 / 1500
Refrigerant, additional quan. >5m g/m 20 40
Refrigerant piping, max. length m 25 25 30 45
Refrigerant piping, max. height m 10 10 15 20
Refrigerant connection
Liquid line
Zoll
(mm)
1/4 (6,35) 1/4 (6,35) 1/4 (6,35) 3/8 (9,52)
Refrigerant connection
Suction pipe
Zoll
(mm)
3/8 (9,52) 3/8 (9,52) 1/2 (12,70) 5/8 (15,90)
Dimensions: H/W/D mm 590/760/285 700/845/320
Weight kg 35 35 36 50
Ref. no. 1623108 1623118 1623128 1623138
1)
Air inlet temp. TK 27°C / FK 19°C, outside temp. TK 35°C, FK 24°C, max. air flow volume, 5m pipe length
2)
Air inlet temp. TK 20°C, outside temperature TK 7°C, FK 6°C, max. air flow volume, 5m pipe length
3)
The specified value is based on results from standard testing.
The actual consumption depends on the use and location of the unit
4)
The specified value is based on the average heating period
5)
At distance of 1m in the open air; specified values are maximum values
6)
Contains greenhouse gas according to Kyoto protocol, GWP 1975 (for further info, see chapter "Adding refrig.")
9