EasyManuals Logo

Renogy MPPT Series User Manual

Renogy MPPT Series
29 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
!
16
on the load after 10 minutes delay for several hours which users set on the timer.
The timer setting operation is referred to as “Load Work Mode Setting”.
3. Test Mode
It is used to test the system and the same as Dusk to Dawn. But there is no 10-
minute delay when controller recognizes the starting voltage. When below the
starting voltage, the controller will turn on the load, if higher, it will turn off load.
The test mode makes it easy to check the system installation.
4. Manual Mode
This mode is to turn on/off the load by the Setting button.
Load Work Mode Setting
Figure 4-5 Instruction figure on setting
Press the setting button once and the setting indicators will be changed once
among Timer 1, Timer 2 and battery type.
When Timer 1 setting indicator is on, press the setting button for more than 5
seconds until the LED digital display flashes. Then press the setting button until
the desired number appears according to the Table 4-6. The setting is finished
when the digital display stops flashing.
Likewise, Timer 2 set-up instructions are the same as Timer 1 using Table 4-7 as
reference.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Renogy MPPT Series and is the answer not in the manual?

Renogy MPPT Series Specifications

General IconGeneral
Max Battery Voltage32V
TypeMPPT
Rated Charge Current20A, 30A, 40A, 60A
Nominal System Voltage12V/24V auto detect
Max PV Input Voltage100VDC
CommunicationRS232, Bluetooth
Maximum PV Input Power260W/12V; 520W/24V (20A), 390W/12V; 780W/24V (30A), 520W/12V; 1040W/24V (40A), 780W/12V; 1560W/24V (60A)
Max Solar Input Current20A, 30A, 40A, 60A

Related product manuals