RPH 12
PUSH
DTRPO
Switch-on temperature diff.
Adjustment range: 1.0 50.0 K
Factory setting: 6.0 K
RPH
Return preheating
Selection: ON / OFF
Factory setting: OFF
DTRPF
Switch-on temperature diff.
Adjustment range: 0.5 49.5 K
Factory setting: 4.0 K
MNRPH
Minimum limitation
Adjustment range:
0.5 89.5 °C
Factory setting: 30.0 °C
12
Return preheating
The return preheating function can be used for transferring heat from a heat source
to the heating circuit return.
The relay (system-dependent) is energised when both switch-on conditions are fullled:
the temperature difference between the sensors store return and heating circuit
return has exceeded the switch-on temperature difference.
the temperature at the heating circuit return has exceeded the minimum temperature.
The switch-on hysteresis is -5 K.
12
OK
14
OFF
ON
BACK
PUSH
REL (2, 3) / Relay control
Selection: ONOF, Puls,
PSOL, PHEA, 0 - 10, ADAP
Factory setting: PSOL
REL 13
PUSH
MAX (2, 3) / Maximum speed
Adjustment range: 20 … 100 %
Factory setting: 100 %
MIN (2, 3) / Minimum speed
Adjustment range: 20 … 100 %
Factory setting: 30 %
13
Relay control
With this parameter, the relay control type can be adjusted. The following types
can be selected:
Adjustment for standard pump without speed control
OnOF : Pump on / pump off
Adjustment for standard pump with speed control
PULS : Burst control via semiconductor relay
Adjustment for high-efciency pump (HE pump)
PSOL : PWM prole solar pump
PHEA : PWM prole heating pump
0-10 : Speed control via 0 - 10 V signal
ADAP : Speed control signal via a VBus
®
/ PWM interface adapter
Note:
For more information about connecting HE pumps, see page 36.
Minimum speed
In the adjustment channel MIN(2, 3) a relative minimum speed for connected
pumps can be allocated to the outputs R1, R2 and R3.
Note:
When loads which are not speed-controlled (e. g. valves) are used, the pump
speed value of the corresponding relay must be set to 100 % or the control
type must be set to ONOF in order to deactivate pump speed control.
Maximum speed
In the adjustment channel MAX(2, 3) a relative minimum speed for connected
pumps can be allocated to the outputs R1, R2 and R3.
Note:
When loads which are not speed-controlled (e. g. valves) are used, the pump
speed value of the corresponding relay must be set to 100 % or the control
type must be set to ONOF in order to deactivate pump speed control.
Relay allocation for PWM outputs
A relay can be allocated to the PWM outputs PWMA and PWMB in the
PWMA(B) channel.
13
PWMA / Relay allocation
Adjustment range: 1 … 3
Factory setting: 1
PWMB / Relay allocation
Adjustment range: 1 … 3
Factory setting: 2
OK
ONOF Puls, PSOL,
PHEA,
0 - 10, ADAP
BACK
PUSH