Manual mode
For control and service work, the operating mode of the relays can be manually
adjusted. For this purpose, select the adjustment channel MAN1(2, 3, 4) (for R1, 2,
3, 4) in which the following adjustments can be made:
Operating mode
AUTO : relay in automatic mode
OFF : relay is switched off
MIN : relay is switched with adjusted minimum speed (not if REL = ONOF)
MAX : relay is switched with adjusted maximum speed
Note:
After service and maintenance work, set the relay mode back to AUTO.
Normal operation is not possible in manual mode.
Note:
For information about the control LED in the Lightwheel
®
see page 37.
MAN 15
PUSH
BLPR 16
PUSH
MAN1 (2, 3)
Adjustment range: AUTO,
ON, OFF, MIN, MAX
Factory setting: AUTO
BLPR
Adjustment range: ON / OFF
Factory setting: OFF
MAN4
Adjustment range:
AUTO, ON, OFF
Factory setting: AUTO
16
Blocking protection
In order to protect the pumps against blocking after standstill, the controller is
equipped with a blocking protection function. This function switches on the relays
one after another every day at 12:00 a.m. for 10 s at 100 %.
OK
OK
16
17
BACK
PUSH
Note:
The adjustments described in this chapter are independent of those in the
COOL menu, which are inactive during a holiday.
Note:
If the drainback option is activated, the holiday function will also not be
available and cannot be selected by means of the micro button
.
Note:
If the holiday function is activated, the drainback option will not be avail-
able.
AHOFF
Holiday afterheating
Selection: ON / OFF
Factory setting: OFF
DHW heating
BACK
PUSH
HDSEN
Heat dump sensor
Selection: 1 … 6
Factory setting: 3
HDREL
Heat dump relay
Selection: 1 … 3
Factory setting: 3
a
d ecb
15
14